Technical data

ISSUE 2
11
TEST FOR SPILLAGE
CHECK FOR SATISFACTORY CLEARANCE OF COMBUSTION PRODUCTS
CLOSE ALL DOORS AND WINDOWS IN THE ROOMS CONTAINING THE
FIRE.
TURN ON GAS FIRE AND SET THE CONTROL TO HIGH
LEAVE THE FIRE BURNING FOR FIVE MINUTES AND INSERT A LIGHTED
SMOKE MATCH ON A VERTICAL PLANE
50 mm DIRECTLY UNDER FRONT EDGE OF CANOPY AND 50mm FROM
EITHER SIDE OF THE OPENING
ALL SMOKE MUST BE DRAWN INTO THE FLUE
IF SPILLAGE OCCURS ALLOW A FURTHER TEN MINUTES
SHOULD SPILLAGE STILL OCCUR TURN OFF THE FIRE AND SEEK
EXPERT ADVICE
IF AN EXTRACTOR FAN IS SITUATED IN THE ROOM , THIS TEST SHOULD
BE REPEATED WITH THE FAN RUNNING
IF THERE IS A ROOM WITH AN EXTRACTOR FAN, THE TEST SHOULD BE
REPEATED WITH ALL THE DOORS TO THAT ROOM OPENED AND THE
EXTRACTOR FAN RUNNING
FITTING TRIMS
FIT THE TRIM WITH FOUR MAGNETS PLACED ON THE VERTICAL SIDE FLANGES
OF THE FIREBOX (ONE AT THE TOP AND ONE AT THE BOTTOM)
OFFER THE TRIM UP AND PUSH INTO POSITION
PLACE FRET CENTRALLY IN FRONT TO COVER THE CONTROLS
INSTRUCT USER
DEMONSTRATE THE LIGHTING AND EXTINGUISHING PROCEDURES TO THE USER
AND REMOVAL AND REFITTING OF THE TRIM FOR CLEANING.
THE APPLIANCE SHOULD BE OPERATED WITH THE GAS CONTROL NOT TURNED ON
MORE THAN LOW FOR THE FIRST FIVE HOURS OF USE TO ALLOW THE FIBRE
FUEL TO CURE SLOWLY.
THE CURING EFFECT OF HEATING THE FUEL AND OTHER CERAMICS COMPONENTS
WILL CAUSE AN INITIAL ODOR.
THE APPLIANCE SHOULD BE SERVICED ANNUALLY BY A COMPETENT PERSON IN
ACCORDANCE WITH THESE INSTRUCTIONS AND THE APPLIANCE CHECKED FOR
SPILLAGE IN ACCORDANCE WITH THE METHOD DETAILED IN THESE
INSTRUCTIONS
HAND THESE INSTRUCTIONS TO THE USER.