Operating instructions

PROGRAMMING 15
Press to increase or
to decrease
Press simultaneously
Press to change
Press to increase or
to decrease
Press to increase or
to decrease
Press to increase or
to decrease
Press to increase or
to decrease
5. Press status again, this displays the Backwash Time in minutes. The
setting can be adjusted between 5 and 40 minutes by using the up and
down arrows. A number “5” will appear at the bottom of the display while
in this mode.
6. Press status again to display the Brine/Rinse Time in minutes. The
settings can be adjusted using the up and down arrows (35-99 min). A
number “6” will appear at the bottom of the display while in this mode.
7. Press status again to display the Hardness Level in grains per gallon. The
setting can be adjusted from 2-99 gpg by using the up and down arrows.
This screen will not appear when the Aqua-Sensor
®
probe is attached. A
number “7” will appear at the bottom of the display while in this mode.
8. Press status again, for time clock models the display will show the
Regeneration Interval. The setting can be adjusted using the up and
down arrows. Controls with a Soft-Minder
®
meter will display the Gallons
to Signal (multiply the displayed value by 10). A number “8” will appear at
the bottom of the display while in this mode.
8A. Display menu '8A' will light when dip switch #10 is in the ON position.
This is the Time Clock Backup feature. The control will force a regeneration,
within a range of 1-42 days, when in Aqua-Sensor
®
or Soft-Minder
®
meter
mode.
9. Pressing status again will display the Lock/Unlock feature. A “U” in the
display signifies an unlocked microprocessor, while a “L” will lock the
settings except for the time of day. To toggle between the two settings
press both arrow keys simultaneously. A number “9” will appear at the
bottom of the display while in this mode.
10. Pressing status again brings up the ability to Enable/Disable the screen
blanking. To have the display constantly lit, press the up arrow, a “d” for
disable will appear in the display. Pressing the up arrow again displays an
“E”, signifying that display blanking is enabled. A number “10” will appear
at the bottom of the display while in this mode.
NOTICE: Programming changes are not locked into the microprocessor memory until the control completes a
regeneration cycle. To initiate a manual regeneration, press the REGEN. button twice, the "REGEN" enunciator
will flash on the display. Refer to the Manual Cycling section on how to step through the regeneration stages.