Daikin.TCF.020 95951-KRQ/ECMC99-4476. Daikin.TCF.020 95951-KRQ/ECMC99-4476. Daikin.TCF.020 95951-KRQ/ECMC99-4476. Daikin.TCF.020 95951-KRQ/ECMC99-4476. Daikin.TCF.020 95951-KRQ/ECMC99-4476. Daikin.TCF.020 95951-KRQ/ECMC99-4476. Daikin.TCF.020 95951-KRQ/ECMC99-4476. Daikin.TCF.020 95951-KRQ/ECMC99-4476. Daikin.TCF.020 95951-KRQ/ECMC99-4476. Noboru Murata Manager Quality Control Department Shiga, 1st of Jan. 2006 Daikin.TCF.020 95951-KRQ/ECMC99-4476 Daikin.TCF.020 95951-KRQ/ECMC99-4476. Daikin.TCF.
01_EN_3P159684-2F.fm Page 1 Wednesday, December 7, 2005 3:18 PM Safety Precautions • Read these Safety Precautions carefully to ensure correct installation. • This manual classifies the precautions into WARNING and CAUTION. Be sure to follow all the precautions below: they are all important for ensuring safety. WARNING...............Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury. CAUTION...............
01_EN_3P159684-2F.fm Page 2 Wednesday, December 7, 2005 3:18 PM Accessories Accessories supplied with the outdoor unit: (B) Drain plug (Heat pump-Models) (A) Installation Manual 1 1 There is on the bottom packing case. Precautions for Selecting the Location 1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
01_EN_3P159684-2F.fm Page 3 Wednesday, December 7, 2005 3:18 PM Outdoor Unit Installation Drawings Wrap the insulation pipe with the finishing tape from bottom to top. 50 class Model 60 class Max. allowable length 30m Min. allowable length 1.5m Max. allowable height 20m Additional refrigerant required for refrigerant pipe exceeding 10m in length. 20g/m Gas pipe Liquid pipe O.D. 12.7mm 71 class O.D. 15.9mm O.D. 6.4mm CAUTION Set the piping length from 1.5m to 30m.
01_EN_3P159684-2F.fm Page 4 Wednesday, December 7, 2005 3:18 PM Installation Guidelines • Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines below. • For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
01_EN_3P159684-2F.fm Page 5 Wednesday, December 7, 2005 3:18 PM Outdoor Unit Installation 3. Flaring the Pipe End 1) Cut the pipe end with a pipe cutter. 2) Remove burrs with the cut surface facing downward so that the chips do not enter the pipe. 3) Put the flare nut on the pipe. 4) Flare the pipe. 5) Check that the flaring is properly made. (Cut exactly at right angles.) Remove burrs Flaring Set exactly at the position shown below.
01_EN_3P159684-2F.fm Page 6 Wednesday, December 7, 2005 3:18 PM 5. Purging Air and Checking Gas Leakage • When piping work is completed, it is necessary to purge the air and check for gas leakage. WARNING 1) 2) 3) 4) Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle. When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
01_EN_3P159684-2F.fm Page 7 Wednesday, December 7, 2005 3:18 PM Outdoor Unit Installation 6. Refilling The Refrigerant Check the type of refrigerant to be used on the machine nameplate. Precautions when adding R410A Fill from the liquid pipe in liquid form. It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation. 1) Before filling, check whether the cylinder has a siphon attached or not.
01_EN_3P159684-2F.fm Page 8 Wednesday, December 7, 2005 3:18 PM Pump Down Operation In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 1) Remove the valve lid from liquid shut-off valve and gas shutoff valve. 2) Carry out forced cooling operation. 3) After five to ten minutes, close the liquid shut-off valve with a hexagonal wrench. 4) After two to three minutes, close the gas shut-off valve and stop forced cooling operation.
01_EN_3P159684-2F.fm Page 9 Wednesday, December 7, 2005 3:18 PM Wiring WARNING 1) Do not use tapped wires, stand wires, extensioncords, or starbust connections, as they may cause overheating, electrical shock, or fire. 2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the terminal block.) Doing so may cause electric shock or fire. 3) Be sure to install an earth leak detector. (One that can handle higher harmonics.
01_EN_3P159684-2F.fm Page 10 Wednesday, December 7, 2005 3:18 PM CAUTION When connecting the connection wires to the terminal board using a single core wire, be sure to perform curling. Problems with the work may cause heat and fires. z Stripping wire at terminal block 3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop. Test Run and Final Check 1. Trial Operation and Testing.