Install Instructions

Danfossvalves are manufactured to
the highest standards and have been
independently tested and conform to
ASHRAE 102-1983.
4. STANDARD
Brass products such as Danfoss valves
should not be installed in hydronic
heating systems which are being
treated with medias that contain - or
that during the process of treatment
could develop, agents agressive to
brass. In concentrations larger than
shown, agents such as Ammonia (0.2
mg/l), Mercury (0.01 mg/l), Oxygen
(0.05 mg/l), Carbondioxide (0.05 mg/l),
Cloride (20 mg/l) must be avoided.
Further the pH-value of the uid in the
hydronic heating system in contact
with the brass products should not
exceed 9.5.
Neglecting the above restrictions
may in some circumstances cause
damage to the brass in the valve
allowing the heating uid to escape,
possibly scalding any bystanders.
5. WARNING
To avoid internal damage and void of
warranty mineral oils must not come in
contact with EPDM valve components..
6. NOTE