User Guide

Installation guide
Thermostat
Type KPU
© Danfoss A/S (AC-MC / jmn), 2014-02 DKRCC.PI.CD0.A3.22 / 520H8467 1
060R9769
060R9769
Application
KPU thermostats are used for regulation and to ensure safety
in refrigeration, freezing, air conditioning, ventilating and
heating systems.
KPU thermostats are available with vapor charge or with
adsorption charge.
All KPU thermostats are tted with Single-Pole Double-Throw
(SPDT) switches.
For large a.c. motors and for all d.c. motors, KPU is installed
in the control circuit. For single phase ac motors, KPU
is installed in the line voltage supply to the motor.
The standard KPU enclosure is rated NEMA 1.
NEMA 1 is obtained when the thermostat is mounted on a at
surface. When mounting KPU on a bracket, cover all unused
holes.
Product Specication
Thermostat bulb types
Charge Type Code no. Bulb type
Capillary tube
length
Reset
function
Regulating
range
Dierential Δt
Max. bulb
temperature
Ambient
temperature
[in.]
[°F] [°F] [°F] [°F]
Vapor
KPU 61 060L5201 A 80 auto. -20 – 60 4 – 18
2)
250
-40 – 122
(170 for max.
2 hours)
KPU 61 060L5203 B 80 auto. -20 – 60 4 – 18
2)
250
KPU 61B 060L5204 B 80 man. (min.)
1)
-20 – 60 5 (xed)
2)
250
KPU 61B 060L5205 B 200 man. (min.)
1)
-20 – 60 5 (xed)
2)
250
KPU 61 060L5210 B 80 auto. -20 – 60 4 – 18
2)
250
KPU 62 060L5206 C1 0 auto. -20 – 60 4 – 18
2)
250
KPU 63 060L5213 A 80 auto. -60 – 15 10 – 25
2)
250
KPU 63 060L5214 B 80 auto. -60 – 15 10 – 25
2)
250
KPU 68 060L5215 C1 0 auto. 25 – 95 5 – 22
2)
250
KPU 69 060L5217 B 80 auto. 25 – 95 5 – 22
2)
250
Adsorption
KPU 62 060L5207 C2 0 auto. -20 – 60 4 – 15 175
KPU 73 060L5208 E3 80 auto. -15 – 60 5 – 35 175
KPU 73 060L5209 E1 80 auto. -15 – 60 15 – 45 175
KPU 73B 060L5211 E3 80 man. (min.)
1)
-15 – 60 6 (xed) 175
KPU 73 060L5212 D 80 auto. -15 – 60 5 – 35 175
KPU 71 060L5218 E2 80 auto. 25 – 70 5 – 18 175
KPU 71B 060L5216 E2 80 man. (min.)
1)
25 – 70 5 (xed) 175
KPU 74 060L5219 E1 80 auto. 0 – 80 9 – 35 175
KPU 74B 060L5220 E1 80 man. (min.)
1)
0 – 80 10 (xed) 175
KPU 75 060L5221 F 80 auto. 30 – 95 5 – 18 230
KPU 77 060L5223 E3 80 auto. 60 – 140 6 – 18 265
1)
man. (min.): Manual reset after cut-out on falling temperature.
2)
The switch dierential is dependent on range settings. Low range settings increases the dierential.
High range settings decreases the dierential. Use the graphs on page 3 to determine the correct dierential setting.
A B C D E F
straight capillary tube remote air coil air coil/room sensor double contact remote coil remote bulb remote duct coil