Submittal Sheet

2 DKRCC.PD.AXV.A9.02 / 520H8187 © Danfoss A/S (AC-MCI/sw) 2013-11
Data sheet Thermostatic expansion valves, type TGE
Refrigerant
Range K
–25 - +10 °C / –15 - +50 °F
MOP point for evaporating temperature t
e
and evaporating pressure p
e
t
e
= +15 °C/+60 °F
R22 100 psig / 6.9 bar (abs)
R407C 95 psig / 6.6 bar (abs)
R134a 55 psig / 5 bar (abs)
R410A 165 psig / 11.5 bar (abs)
R404A/ R507 120 psig / 8.3 bar (abs)
1
) MOP for R290, R32, please contact Danfoss for more info.
Operating conditions Max. operating temperature
- Thermostatic element
MAH charge: 150 °C / 302 °F
N charge: 100 °C / 210 °F (R410A)
K charge: 150 °C / 302 °F (R410A)
Valve body: 110 °C / 230 °F
MOP function
Identication Importat valve information is provided on the
diaphragm element (g. 1)
Main valve example:
TGE = Valve type
9 TR = Nominal capacity Q
nom
in tons
of refrigeration
32 kW = Rated capacity Q
nom
in kW
R410A = Refrigerant
−25 / +10 °C = Evaporating temperature range (°C)
−15 / + 50 °F = Evaporating temperature range (°F)
067N3006 = Code number
MOP = Max. Operating Pressure
PS 46 bar /
MWP 667 psig = Max. Working Pressure in bar and psig
BE2211E: BE = China
22 = week
11 = 2011
E = friday
Fig. 1
Refrigerant code:
R22 = X
R410A/R32 = L
R410A = L
R407C = Z
R134a = N
R404A/R507 = S
R290 = -
Max. working pressure 46 bar / 667 psig
Max. test pressure 51 bar / 740 psig
TGE valves are designed for biow operations.
Valve options In addition to the standard programme, variants
of following options may be available:
- Refrigerants
- Evaporating temperature range
- MOP point
- Static superheat setting (0K / 0 °F - 8K / 14.4 °F)
- Flare connections
Please contact your nearest Danfoss sales oce
to discuss valve options.
Technical data
Capillary tube length
Type Inlet ODF solder Outlet ODF solder
TGE 10
3
/
8
, ½ ,
5
/
8
5
/
8
,
7
/
8
,
1-
1
/
8
10 , 12 , 16 16, 22, 28
TGE 20
TGE 40
5
/
8
,
7
/
8
, 1-
1
/
8
5
/
8
,
7
/
8
,
1-
1
/
8
,
1-
3
/
8
16, 22, 28 16, 22, 28, 35
Type Capillary tube length
TGE 10 1.5 m 59 in.
TGE 20 1.5 m or 3 m 59 in. or 118 in.
TGE 40 1.5 m or 3 m 59 in. or 118 in.
Connection
Thermostatic charge for R410A/R32, R22/R407C,
R134a, R407C, R404A/R507, R410A and R290:
MAH –30 - +15 °C
–22 - +60 °F
For Air Conditioning applications
N –40 - +10 °C without MOP
–40 - +50 °F without MOP
For refrigeration applications
K –25 - +10 °C MOP + 15 °C
–15 - +50 °F MOP + 60 °F
For refrigeration applications
Static superheat (SS): 4K / 7.2°F