Install Instructions

Cable Strapping
Should the Danfoss cable strapping ( part # 088L1051, # 088L1050 ) be used for the TX-FH cable,
follow the instructions below for ease of installation.
Secure the Danfoss
strapping to the
ground surface
(3 feet apart)
Place the TX-FH cable
Clip the TX-FH cable
in place
6
General TX-FH Cable Installation Guidelines
The TX-FH cable must be laid out with even spacing over the entire area to be heated. To ensure an
accurate and easy method of installing the TX-FH cable it is recommended to use Danfoss cable
strapping. The strapping should be laid perpendicular to the direction the cable will be unrolled.
Space the strapping 3ft (90cm) apart. Secure the heating cable to the cable strapping at the correct
center-to-center distance. Do not secure the cable too tightly as this may damage the cable.
If wire mesh is available, the cable strapping is not required. The heating cable can be attached
directly to the rebar or wire mesh using tie wraps.
The heating cable can be also secured with hot melt glue, duct tape or 3/8” crown staples.
Danfoss TX-FH Typical Installations
Finished Flooring ( tiles, marble etc.)
Directly on concrete.
Sensor
Mud Bed
Heating Cable ( max. 2” from surface)
Subfloor
Insulation ( optional)
Finished Flooring ( tiles, marble etc.)
Mud Bed
Heating Cable ( max. 2” from surface)
Sensor
Insulation ( optional)
Directly on plywood.
Installing the heating cable
Copyright 2009 Danfoss Inc.
TEL: 866-676-8062. FAX: 905-285-2055
NA.EFHTH-FHM- 07/2009