User Guide
Table Of Contents
- 2. Menu Overview
- 3. Introduction
- 4. General Operation
- 5. Ground Fault: (GFCI) 1/2
- 5. Ground Fault: (GFCI) 2/2
- 6. Icons 1/2
- 6. Icons 2/2
- 7. Startup Wizard
- 8. Programed Heating Schedule
- 9. Operating Choices
- 10. Thermostat Setup Menu 
- 10.1 Heating Schedule 1/2 
- 10.1 Heating Schedule 2/2 
- 10.2 Energy Use 
- 10.3. User Settings 
- 10.4 Installer Settings 
- 10.4.1 Adaptive Function 
- 10.4.2 Open Window 
- 10.4.3 Sensor Application 1/2 
- 10.4.3 Sensor Application 2/2 
- 10.4.4 Sensor Type 1/2 
- 10.4.4 Sensor Type 2/2 
- 10.4.5 Floor Sensor Calibration 
- 10.4.6 Room Sensor Calibration 
- 10.4.7 Floor Protection 1/2 
- 10.4.7 Floor Protection 2/2 
- 10.4.8 Factory Reset 
- 11. Factory Settings
- 12. Troubleshooting 1/2
PAGE 56
© 2015 OJ Electronics A/S
10.4.5 Floor Sensor Calibration
This option allows you to calibrate the floor sensor.
You can calibrate the sensor if the temperature reading diers from the actual floor
temperature.
Note that changes to floor sensor characteristics may damage certain floors.
You can calibrate the sensor with ±17°F or ±10°C in steps of 1°F or 0.5°C in the
following way:
1. Tap the “Menu” button on the home screen.
2. Then tap the “Installer Settings” button to access the various installer settings.
3. Tap the “Floor Sensor Calibration” button.
4. Use the “Arrow Up” or “Arrow Down” button to set the floor temperature
actually measured.
5. Confirm that you want to calibrate the sensor with “√” or cancel with “X”. If the
temperature is confirmed with “√”, a confirmation screen will be displayed briefly.
The thermostat will automatically return to “Installer Settings”.