User Guide
Table Of Contents
- 2. Menu Overview
- 3. Introduction
- 4. General Operation
- 5. Ground Fault: (GFCI) 1/2
- 5. Ground Fault: (GFCI) 2/2
- 6. Icons 1/2
- 6. Icons 2/2
- 7. Startup Wizard
- 8. Programed Heating Schedule
- 9. Operating Choices
- 10. Thermostat Setup Menu 
- 10.1 Heating Schedule 1/2 
- 10.1 Heating Schedule 2/2 
- 10.2 Energy Use 
- 10.3. User Settings 
- 10.4 Installer Settings 
- 10.4.1 Adaptive Function 
- 10.4.2 Open Window 
- 10.4.3 Sensor Application 1/2 
- 10.4.3 Sensor Application 2/2 
- 10.4.4 Sensor Type 1/2 
- 10.4.4 Sensor Type 2/2 
- 10.4.5 Floor Sensor Calibration 
- 10.4.6 Room Sensor Calibration 
- 10.4.7 Floor Protection 1/2 
- 10.4.7 Floor Protection 2/2 
- 10.4.8 Factory Reset 
- 11. Factory Settings
- 12. Troubleshooting 1/2
PAGE 58
© 2015 OJ Electronics A/S
10.4.7 Floor Protection 1/2
This option ensures that the floor temperatures are kept within range.
There are four dierent settings:
• Laminate–themaximumoortemperatureitsetto82°F/28°C
Note that floor temperature can rise by no more than 1.67°F/0.93°C per
10 minutes when Laminate is chosen.
If you want your floor to heat faster, Custom should be used.
• Tile–themaximumoortemperatureissetto104°F/40°C
• Disabled–theoorisnotprotectedagainstexcessiveheating
• Custom–youcandenetheminimumandmaximumtemperaturesthattheoor
is permitted to reach.
The maximum temperature limit protects wooden floors from excessive heat.
The minimum temperature limit prevents the floor from becoming uncomfortably
cold when heating is not needed, e.g. in a bathroom with tiles.
The minimum temperature limit can also be used as frost protection.
Note that the minimum temperature function will increase energy consumption.
Although it is still possible to set the target temperature/setpoint to a value higher
than the floor protection limit, the floor temperature will be prevented from reaching
a temperature higher than that defined here if the system has been installed
according to the Quick Guide.
1
1
2
3
4
>
<
Contents