Specifications

Miscellaneous:
Advanced Vecter Control
Analog Inputs
The analog inputs are used for controlling various
functions of the frequency converter.
There are 2 types of analog inputs:
Current input, 0-20 mA and 4-20 mA
Voltage input, 0-10 V DC.
Analog Outputs
The analog outputs can supply a signal of 0-20 mA, 4-20
mA, or a digital signal.
Automatic Motor Adaptation, AMA
AMA algorithm determines the electrical parameters for
the connected motor at standstill.
Brake Resistor
The brake resistor is a module capable of absorbing the
brake power generated in regenerative braking. This
regenerative braking power increases the intermediate
circuit voltage and a brake chopper ensures that the
power is transmitted to the brake resistor.
CT Characteristics
Constant torque characteristics used for screw and scroll
refrigeration compressors.
Digital Inputs
The digital inputs can be used for controlling various
functions of the frequency converter.
Digital Outputs
The frequency converter features 2 Solid State outputs that
can supply a 24 V DC (max. 40 mA) signal.
DSP
Digital Signal Processor.
Relay Outputs
The frequency converter features 2 programmable Relay
Outputs.
ETR
Electronic Thermal Relay is a thermal load calculation
based on present load and time. Its purpose is to estimate
the motor temperature.
GLCP
Graphical Local Control Panel (LCP102)
Initialising
If initialising is carried out (14-22 Operation Mode), the
programmable parameters of the frequency converter
return to their default settings.
Intermittent Duty Cycle
An intermittent duty rating refers to a sequence of duty
cycles. Each cycle consists of an on-load and an off-load
period. The operation can be either periodic duty or none-
periodic duty.
LCP
The Local Control Panel makes up a complete interface for
control and programming of the frequency converter. The
LCP is detachable and can be installed up to 3 metres
from the frequency converter, i.e. in a front panel by
means of the installation kit option.
The LCP is available in 2 versions:
-
Numerical LCP101 (NLCP)
-
Graphical LCP102 (GLCP)
lsb
Least significant bit.
MCM
Short for Mille Circular Mil, an American measuring unit for
cable cross-section. 1 MCM 0.5067 mm
2
.
msb
Most significant bit.
NLCP
Numerical Local Control Panel LCP 101
On-line/Off-line Parameters
Changes to on-line parameters are activated immediately
after the data value is changed. Press [OK] to activate
changes to off-line parameters.
PID Controller
The PID controller maintains the desired speed, pressure,
temperature, etc. by adjusting the output frequency to
match the varying load.
RCD
Residual Current Device.
Set-up
Save parameter settings in 4 Set-ups. Change between the
4 parameter Set-ups and edit one Set-up, while another
Set-up is active.
SFAVM
Switching pattern called Stator Flux oriented Asynchronous
V ector M odulation (14-00 Switching Pattern).
Slip Compensation
The frequency converter compensates for the motor slip
by giving the frequency a supplement that follows the
measured motor load keeping the motor speed almost
constant.
Smart Logic Control (SLC)
The SLC is a sequence of user-defined actions executed
when the associated user-defined events are evaluated as
true by the SLC.
Thermistor
A temperature-dependent resistor placed where the
temperature is to be monitored (frequency converter or
motor).
Trip
A state entered in fault situations, e.g. if the frequency
converter is subject to an over temperature or when the
frequency converter is protecting the motor, process or