Specifications

7.1.11 Fixed Variable Speed Pump Wiring Diagram
L1/L2/L3 L1/L2/L3 L1/L2/L3
Power Section
RELAY 1
RELAY 2
130BA376.10
Illustration 7.9 Fixed Variable Speed Pump Wiring Diagram
7.1.12
Lead Pump Alternation Wiring
Diagram
130BA377.13
L1/L2/L3
FC
L1/L2/L3
L1/L2/L3
k3
k2
k3
k1
K2
K1
K1
K1
K4
K3
K4
K3
R1
R2
Illustration 7.10 Lead Pump Alternation Wiring Diagram
Every pump must be connected to 2 contactors (K1/K2 and
K3/K4) with a mechanical interlock. Thermal relays or other
motor protection devices must be applied according to
local regulation and/or individual demands.
RELAY 1 (R1) and RELAY 2 (R2) are the built-in
relays in the frequency converter.
When all relays are de-energised, the first built in
relay to be energised cuts in the contactor
corresponding to the pump controlled by the
relay. E.g. RELAY 1 cuts in contactor K1, which
becomes the lead pump.
K1 blocks for K2 via the mechanical interlock
preventing mains to be connected to the output
of the frequency converter. (via K1).
Auxiliary break contact on K1 prevents K3 to cut
in.
RELAY 2 controls contactor K4 for on/off control
of the fixed speed pump.
At alternation both relays de-energises and now
RELAY 2 is energised as the first relay.
Application Examples Design Guide
MG11BC02 Danfoss A/S © Rev. 06/2014 All rights reserved. 127