Specifications

2
Introduction to VLT
®
HVAC Drive
2.1 Safety
2.1.1 Safety Note
WARNING
The voltage of the frequency converter is dangerous
whenever connected to mains. Incorrect installation of
the motor, frequency converter or fieldbus may cause
death, serious personal injury or damage to the
equipment. Consequently, the instructions in this
manual, as well as national and local rules and safety
regulations, must be complied with.
Safety Regulations
1. Disconnect the frequency converter from mains, if
repair work is to be carried out. Check that the
mains supply has been disconnected and that the
necessary time has elapsed before removing
motor and mains plugs.
2. The [Stop/Reset] key on the LCP of the frequency
converter does not disconnect the equipment
from mains and is thus not to be used as a safety
switch.
3. Established correct protective earthing of the
equipment, protect the user against supply
voltage, and protect the motor against overload
in accordance with applicable national and local
regulations.
4. The earth leakage currents are higher than 3.5
mA.
5. Protection against motor overload is set by
1-90 Motor Thermal Protection. If this function is
desired, set 1-90 Motor Thermal Protection to data
value [ETR trip] (default value) or data value [ETR
warning]. Note: The function is initialised at 1.16 x
rated motor current and rated motor frequency.
For the North American market: The ETR
functions provide class 20 motor overload
protection in accordance with NEC.
6. Do not remove the plugs for the motor and
mains supply while the frequency converter is
connected to mains. Check that the mains supply
has been disconnected and that the necessary
time has elapsed before removing motor and
mains plugs.
7. Note that the frequency converter has more
voltage inputs than L1, L2 and L3, when load
sharing (linking of DC intermediate circuit) and
external 24 V DC have been installed. Check that
all voltage inputs have been disconnected and
that the necessary time has passed before
commencing repair work.
Installation at high altitudes
CAUTION
380-500 V, enclosure types A, B and C: At altitudes
above 2 km, contact Danfoss regarding PELV.
525-690 V: At altitudes above 2 km, contact Danfoss
regarding PELV.
WARNING
Warning against unintended start
1. The motor can be stopped with digital
commands, bus commands, references or a
local stop, while the frequency converter is
connected to mains. If personal safety consider-
ations make it necessary to ensure that no
unintended start occurs, these stop functions
are not sufficient.
2. While parameters are being changed, the motor
may start. Consequently, the [Reset] key must
always be activated; following which data can
be modified.
3. A motor that has been stopped may start if
faults occur in the electronics of the frequency
converter, or if a temporary overload or a fault
in the supply mains or the motor connection
ceases.
WARNING
Touching the electrical parts may be fatal - even after
the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been
disconnected, such as external 24 V DC, load sharing
(linkage of DC intermediate circuit), as well as the motor
connection for kinetic back-up. Refer to the Operating
Instructions for further safety guidelines.
2.1.2
Caution
WARNING
The DC link capacitors remain charged after power has
been disconnected. To avoid an electrical shock hazard,
disconnect the from the mains before carrying out
maintenance. Wait at least as follows before doing
service on the frequency converter: