Specifications

2.7.21 Primary Pumps
Primary pumps in a primary/secondary pumping system can be used to maintain a constant flow through devices that
encounter operation or control difficulties when exposed to variable flow. The primary/secondary pumping technique
decouples the “primary” production loop from the “secondary” distribution loop. This allows devices such as chillers to
obtain constant design flow and operate properly, while allowing the rest of the system to vary in flow.
As the evaporator flow rate decreases in a chiller, the chilled water begins to become over-chilled. As this happens, the
chiller attempts to decrease its cooling capacity. If the flow rate drops far enough, or too quickly, the chiller cannot shed its
load sufficiently and the chiller’s low evaporator temperature safety trips the chiller requiring a manual reset. This situation
is common in large installations especially when 2 or more chillers in parallel are installed if primary/secondary pumping is
not utilised.
2.7.22 The VLT Solution
Depending on the size of the system and the size of the primary loop, the energy consumption of the primary loop can
become substantial.
A frequency converter can be added to the primary system, to replace the throttling valve and/or trimming of the impellers,
leading to reduced operating expenses. 2 control methods are common:
The first method uses a flow meter. Because the desired flow rate is known and is constant, a flow meter installed at the
discharge of each chiller, can be used to control the pump directly. Using the built-in PID controller, the frequency
converter always maintains the appropriate flow rate, even compensating for the changing resistance in the primary piping
loop as chillers and their pumps are staged on and off.
The other method is local speed determination. The operator simply decreases the output frequency until the design flow
rate is achieved.
Using a frequency converter to decrease the pump speed is very similar to trimming the pump impeller, except it does not
require any labour and the pump efficiency remains higher. The balancing contractor simply decreases the speed of the
pump until the proper flow rate is achieved and leaves the speed fixed. The pump operates at this speed any time the
chiller is staged on. Because the primary loop does not have control valves or other devices that can cause the system curve
to change, and the variance due to staging pumps and chillers on and off is usually small, this fixed speed remains
appropriate. In the event the flow rate needs to be increased later in the systems life, the frequency converter can simply
increase the pump speed instead of requiring a new pump impeller.
Introduction to VLT® HVAC D... Design Guide
30 Danfoss A/S © Rev. 06/2014 All rights reserved. MG11BC02
22