Specifications

2.10 Galvanic Isolation (PELV)
2.10.1 PELV - Protective Extra Low Voltage
PELV offers protection by way of extra low voltage.
Protection against electric shock is ensured when the
electrical supply is of the PELV type and the installation is
made as described in local/national regulations on PELV
supplies.
All control terminals and relay terminals 01-03/04-06
comply with PELV (Protective Extra Low Voltage), with the
exception of grounded Delta leg above 400 V.
Galvanic (ensured) isolation is obtained by fulfilling
requirements for higher isolation and by providing the
relevant creepage/clearance distances. These requirements
are described in the EN 61800-5-1 standard.
The components that make up the electrical isolation, as
described below, also comply with the requirements for
higher isolation and the relevant test as described in EN
61800-5-1.
The PELV galvanic isolation can be shown in 6 locations
(see Illustration 2.34):
To maintain PELV, all connections made to the control
terminals must be PELV, e.g. thermistor must be
reinforced/double insulated.
1. Power supply (SMPS) incl. signal isolation of U
DC
,
indicating the voltage of intermediate DC-link
circuit.
2. Gate drive that runs the IGBTs (trigger
transformers/opto-couplers).
3. Current transducers.
4. Opto-coupler, brake module.
5. Internal inrush, RFI, and temperature
measurement circuits.
6. Custom relays.
7. Mechanical brake.
130BC968.10
1
3
25 4
6
b
a
M
7
Illustration 2.34 Galvanic Isolation
The functional galvanic isolation (a and b on drawing) is
for the 24 V back-up option and for the RS-485 standard
bus interface.
WARNING
Installation at high altitude:
380-500 V, enclosure types A, B and C: At altitudes
above 2 km, contact Danfoss regarding PELV.
525-690 V: At altitudes above 2 km, contact Danfoss
regarding PELV.
WARNING
Touching the electrical parts could be fatal - even after
the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been
disconnected, such as load sharing (linkage of DC
intermediate circuit), as well as the motor connection for
kinetic back-up.
Before touching any electrical parts, wait at least the
amount of time indicated in Table 2.19.
Shorter time is allowed only if indicated on the
nameplate for the specific unit.
2.11 Earth Leakage Current
Follow national and local codes regarding protective
earthing of equipment with a leakage current > 3,5 mA.
Frequency converter technology implies high frequency
switching at high power. This generates a leakage current
in the earth connection. A fault current in the frequency
converter at the output power terminals might contain a
DC component which can charge the filter capacitors and
cause a transient earth current.
The earth leakage current is made up of several contri-
butions and depends on various system configurations
including RFI filtering, screened motor cables, and
frequency converter power.
Introduction to VLT® HVAC D...
Design Guide
46 Danfoss A/S © Rev. 06/2014 All rights reserved. MG11BC02
22