Specifications

function to carry out when the power transmitted to the
brake resistor exceeds the limit set in 2-12 Brake Power
Limit (kW).
NOTICE
Monitoring the brake power is not a safety function; a
thermal switch is required for that purpose. The brake
resistor circuit is not earth leakage protected.
Overvoltage control (OVC) (exclusive brake resistor) can be
selected as an alternative brake function in 2-17 Over-
voltage Control. This function is active for all units. The
function ensures that a trip can be avoided, if the DC-link
voltage increases. This is done by increasing the output
frequency to limit the voltage from the DC-link. It is a
useful function, e.g. if the ramp-down time is too short
since tripping of the frequency converter is avoided. In this
situation, the ramp-down time is extended.
NOTICE
OVC cannot be activated when running a PM motor
(when 1-10 Motor Construction is set to [1] PM non salient
SPM).
2.12.4 Brake Resistor Cabling
EMC (twisted cables/shielding)
Twist the wires to reduce the electrical noise from the
wires between the brake resistor and the frequency
converter.
For enhanced EMC performance, use a metal screen.
2.13
Extreme Running Conditions
Short Circuit (Motor Phase Phase)
The frequency converter is protected against short circuits
by current measurement in each of the 3 motor phases or
in the DC-link. A short circuit between 2 output phases
causes an overcurrent in the inverter. The inverter is
turned off individually when the short circuit current
exceeds the permitted value (Alarm 16 Trip Lock).
To protect the frequency converter against a short circuit
at the load sharing and brake outputs, see the design
guidelines.
Switching on the output
Switching on the output between the motor and the
frequency converter is permitted. Fault messages may
appear. Enable flying start to catch a spinning motor.
Motor-generated overvoltage
The voltage in the intermediate circuit is increased when
the motor acts as a generator. This occurs in following
cases:
The load drives the motor (at constant output
frequency from the frequency converter), ie. the
load generates energy.
During deceleration (ramp-down) if the moment
of inertia is high, the friction is low and the ramp-
down time is too short for the energy to be
dissipated as a loss in the frequency converter,
the motor and the installation.
Incorrect slip compensation setting may cause
higher DC-link voltage.
Back-EMF from PM motor operation. If coasted at
high RPM, the PM motor back-EMF may
potentially exceed the maximum voltage
tolerance of the frequency converter and cause
damage. To help prevent this, the value of
4-19 Max Output Frequency is automatically
limited based on an internal calculation based on
the value of 1-40 Back EMF at 1000 RPM,
1-25 Motor Nominal Speed and 1-39 Motor Poles.
If it is possible that the motor may overspeed
(e.g. due to excessive windmilling effects),
Danfoss recommends using a brake resistor.
WARNING
The frequency converter must be equipped with a brake
chopper.
The control unit may attempt to correct the ramp if
possible (2-17 Over-voltage Control).
The inverter turns off to protect the transistors and the
intermediate circuit capacitors when a certain voltage level
is reached.
See 2-10 Brake Function and 2-17 Over-voltage Control to
select the method used for controlling the intermediate
circuit voltage level.
NOTICE
OVC cannot be activated when running a PM motor
(when 1-10 Motor Construction is set to [1] PM non
salient SPM).
Introduction to VLT® HVAC D... Design Guide
MG11BC02 Danfoss A/S © Rev. 06/2014 All rights reserved. 49
2 2