Specifications

Cable-length and cross-section
The frequency converter has been tested with a given
length of cable and a given cross-section of that cable. If
the cross-section is increased, the cable capacitance - and
thus the leakage current - may increase, and the cable
length must be reduced correspondingly. Keep the motor
cable as short as possible to reduce the noise level and
leakage currents.
Switching frequency
When frequency converters are used with Sine-wave filters
to reduce the acoustic noise from a motor, the switching
frequency must be set according to the Sine-wave filter
instruction in 14-01 Switching Frequency.
1. Fasten decoupling plate to the bottom of the
frequency converter with screws and washers
from the accessory bag.
2. Attach motor cable to terminals 96 (U), 97 (V), 98
(W).
3. Connect to earth connection (terminal 99) on
decoupling plate with screws from the accessory
bag.
4. Insert plug connectors 96 (U), 97 (V), 98 (W) (up
to 7.5 kW) and motor cable to terminals labelled
MOTOR.
5. Fasten screened cable to decoupling plate with
screws and washers from the accessory bag.
All types of 3-phase asynchronous standard motors can be
connected to the frequency converter. Normally, small
motors are star-connected (230/400 V, Y). Large motors are
normally delta-connected (400/690 V, Δ). Refer to the
motor name plate for correct connection mode and
voltage.
Procedure
1. Strip a section of the outer cable insulation.
2. Position the stripped wire under the cable clamp
to establish mechanical fixation and electrical
contact between cable screen and ground.
3. Connect ground wire to the nearest grounding
terminal in accordance with grounding
instructions.
4. Connect the 3-phase motor wiring to terminals
96 (U), 97 (V), and 98 (W), see Illustration 6.14.
5. Tighten terminals in accordance with the
information provided in chapter 6.1.1 Torque.
130BD531.10
U
V
W
96
97
98
Illustration 6.14 Motor Connection
130BT333.10
Illustration 6.15 Motor Connection for Enclosure Type B1 and
B2 (IP21/NEMA Type 1, IP55/NEMA Type 12 and IP66/NEMA
Type 4X)
Electrical Installation Design Guide
MG11BC02 Danfoss A/S © Rev. 06/2014 All rights reserved. 87