Datasheet

SIBC R&D VD.DA.E1.02 © Danfoss 08/01 1
Description / Application
Data sheet AIQM
Flow controller with integrated
control valve
Combined with an electric actuator the AIQM
controller is a self-acting flow controller with
integrated control valve. The pressure
difference across the control valve is kept
constantly at 0.2 bar.
The controller is primarily used in district
heating systems for circulation water with a
max. temperature of 150
o
C.
AIQM is used together with following actuators:
- AMV 113 / AME 113 with valve closing
safety function, type tested acc. to DIN 32 730
- AME 110 / AMV 310 / AMV 330
Nominal diameter DN 40 and DN 50
Nominal pressure PN 25
Connection Flange
Flow and return mounting
Type DN
k
vs
Code No.
m
3
/h
AIQM
40 16 003H0160
50 20 003H0161
Ordering
Nominal diameter (DN) 40 50
k
vs
value 16 20
Min. flow rate 1.5 1.5
Nominal flow 10 12
Max. flow rate
1)
12 15
Nominal pressure (PN) 25
Max. pressure difference (bar) 16
z value acc. to VDMA 24 422
2)
0.6
Flow medium Circulation water
Max. medium temperature (
o
C) 150
Type of connection Flange, PN 25 DIN 2501
Approx. valve weight (kg) 9 10
Valve body material Ductile iron GGG 40.3 M. No. EN-JS1025
Seat material Stainless steel M. No. 1.4571
Cone material Brass, stainless steel M. No. 1.4404
Cone seal material EPDM
Valve
Technical data
Effective surface (cm
2
)54
Nominal pressure (PN) 25
Diff. pressure across restrictor (bar) 0.2
Max pressure difference between (bar)
14
(+) chamber and (-) chamber
Material
Body
Stainless steel M. No. 1.4301
Brass, resistant to dezincification
Diaphragm EPDM
Impulse tubes Copper tube Ø 5x1
Approx. weight (kg) 1.5
Actuator
1)
Because of the higher valve
opening factor (Y), the noise level
can be insignificantly higher,
depending on the pressure
ratio (X
F
)
2)
Reference: 0.75 x max. flow
(m
3
/h)

Summary of content (4 pages)