Datasheet

2 VD.DA.E1.02 © Danfoss 08/01 SIBC R&D
Data sheet AIQM, flow controller with integrated control valve
Application examples
Design and operation
1 Electric actuator
2 Stroke adjustment
3 Cone, control valve
4 Seat
5 Cone, flow controller
6 Pressure actuator
Flow mounting
Return mounting
This controller acts as flow limiter as well as
control valve. The pressure actuator keeps a
constant differential pressure across the
control valve of 0.2 bar. The flow limitation is
set by adjusting the stroke of the control
valve's cone.