User manual

5 Manual test
Caution The installation may only be commissioned if the heating system and water heater have been filled and bled.
Otherwise the circulation pump can be damaged.
Caution Any alarms that may occur in connection with the installation must be fault-traced.
5.1 Activate MANUAL TEST
!
Two persons is recommended when doing the manual tests. One at the control display and one at the out-
door unit.
MANUAL TEST has three options:
!
Zero (0): deactivate manual test
!
One (1): activate manual test. This option allows navigating only within the MANUAL TEST menu
!
Two (2): activate manual test with the option of navigating out of the MANUAL TEST menu to check temperatures etc.
Set the heat pump in stand-by mode in the INFORMATION menu:
!
Press left arrow (<) to enter the INFORMATION menu
!
Press right arrow (>) to enter the OPERAT. menu
!
Press right arrow (>)
!
Press button to move down to
(Off)
!
Press right arrow (>) to confirm. The asterisk * is now to the right of
(Off)
!
Press left arrow several times to exit the Information Menu
!
Enter the Service Menu by pressing and holding left (<) arrow for at least 5 seconds.
!
Press button to navigate to the MANUAL TEST entry
!
Press right arrow (>) to enter the MANUAL TEST menu
!
Press + button to select option 2.
!
Press left arrow once to exit
!
The test cases in the table below are available in MANUAL TEST. Required test cases are described in the chap-
ters that follows.
Test cases not described are optional.
Parameter Meaning
COMPRESSOR 0 = stop compressor
1 = start compressor
SYSTEM
CIRC. PUMP
0 = stop system circulation pump
1 = start system circulation pump
CIRC. PUMP 0-10V for test of speed controlled circulation pump.
Depending on type and number of connected circulation pumps, this parameter will contain different informa-
tion.
In the event of pumps with fixed speed, the selection 0 = stop and 1 = start are available
FAN 0–10V for test of the speed controlled fan
FOUR-WAY VALVE 0 = four way valve is set for heating
1 = four way valve is set for defrosting/cooling
EXPANSION VALVE 0 – 100% for test of electronic expansion valve.
SOLENOID 0 = closed solenoid
1 = open solenoid
Commissioning