Technical data

Table Of Contents
6
VMIFI102
1.3 Electrical connection
The electrical installation must only be carried out by
an authorized electrician (and must follow applicable
local and national regulations). The electrical instal-
lation must be carried out using permanently routed
cables. It must be possible to isolate the power sup-
ply using an all-pole circuit breaker for the intended
current. For information regarding maximum load
for externally connected devices, see electrical instal-
lation instructions.
NOTE! The supplied language specific decal for electrical
connection must be adhered to the inside of the door
Electrical current!
The terminal blocks are live and can be highly dan-
gerous due to the risk of electric shock. The power
supply must be isolated before electrical installation
is started. The heat pump is internally connected at
the factory.
Important information
24 VAC 1 must not be connected together with:
• 24 VAC 2
• 24 VDC
• Other equipment that uses 0-10V control signal
• Signal ground GND
24 VAC 2 must only be used as power supply to:
• External equipment that requires 0-10V control
signal
• Auxiliary modules
The two separate 24 VAC circuits must never be con-
nected to each other or to protective ground.
The total power load on 24 VAC 1 respectively 24
VAC 2 must not exceed 50VA.