2. How to Install
2.1. Cabling
2.1.1. Cable Lengths
Baud rate Max total cable
length
Drop length
Maximum per drop Cumulative maxi-
mum
125k baud 500 meters (1640 ft.) 6 meters (20 ft.) for one drop 156 meters (512 ft.)
250k baud 250 meters (820 ft.) 78 meters (256 ft.)
500k baud 100 meters (328 ft.) 39 meters (128 ft.)
2.1.2. Cable Specifications
The cable used should be according to ODVA
specifications.
Be aware that the ODVA “Flat Cable” is an
unscreened cable type, and is not suited for
use with frequency converters.
Illustration 2.1: ODVA “Thin Cable” cross sec-
tion