Operating instructions

Bit 09, Selection of ramp 1/2:
Bit 09 = "0" means that ramp 1 is active (parameters 3-40 to 3-47).
Bit 09 = "1" means that ramp 2 (parameters 3-50 to 3-57) is active.
Bit 10, Data not valid/Data valid:
Is used to tell the frequency converter wheth-
er the control word is to be used or ignored.
Bit 10 = ’0’ causes the control word to be ig-
nored, Bit 10 = ’1’ causes the control word to
be used. This function is relevant, because the
control word is always contained in the tele-
gram, regardless of which type of telegram is
used, i.e. it is possible to turn off the control
word if you do not wish to use it in connection
with updating or reading parameters.
Bit 11, Relay 01:
Bit 11 = "0" Relay not activated.
Bit 11 = "1" Relay 01 activated, provided Con-
trol word bit 11 has been chosen in par. 5-40
Function Relay
.
Bit 12, Relay 04:
Bit 12 = "0" Relay 04 has not been activated.
Bit 12 = "1" Relay 04 has been activated, pro-
vided Control word bit 12 has been chosen in
par. 5-40
Function Relay
.
Bit 13/14, Selection of set-up:
Bits 13 and 14 are used to choose from the
four menu set-ups according to the table to
the right:
Set-up
Bit 14 Bit 13
1 0 0
2 0 1
3 1 0
4 1 1
The function is only possible when Multi-Set-ups is selected in par. 0-10
Active Set-up
.
NB!
In par. 8-55
Set-up Select
a selection is made to define how Bits 13/14 gate with
the corresponding function on the digital inputs.
Bit 15 Reverse:
Bit 15 = ’0’ causes no reversing.
Bit 15 = ’1’ causes reversing.