Operating instructions

5.3.8. Instance 1 Attributes: Explicit Message Instance
Attrib-
ute
Access Name Data
type
Description
1 Get State USINT State of the object
2 Get Instance
Type
USINT Indicates either I/O or Explicit Message
3 Get Transport
Class Trig-
ger
USINT Defines behaviour of the connection
4 Get Produced
Connec-
tion ID
UINT CAN Identifier Field when the connection trans-
mits
5 Get Consumed
Connec-
tion ID
UINT CAN Identifier Field value that denotes message
to be received
6 Get Initial
Communi-
cation
Character-
istics
USINT Defines the message group(s) across which pro-
ductions and consumptions associated with this
connection occur
7 Get Produced
Connectin
size
UINT Maximum number of bytes transmitted across
this connection
8 Get Consumed
Connec-
tion size
UINT Maximum number of bytes received across this
connection
9 Get/Set Expected
Package
Rate
UINT Defines value used in Transmission Trigger Tim-
er and Inactivity/Watchdog timer
12 Get Watchdog
timeout
action
USINT Defines how to handle Inactivity/Watchdog
timeout
13 Get Produced
Connec-
tion Path
Length
UINT Number of Bytes in the produced connection
path attribute
14 Get Produced
Connecti-
no Path
Array of
USINT
Specifies the Application object(s) whose data is
to be produced by these Connection Objects
15 Get Consumd
Connec-
tion Path
Length
UINT Number of bytes in the consumed connection
path attribute
16 Get Consumed
Connec-
tion Path
Array of
USINT
Specifies the Application object(s) that are to re-
ceive the data consumed by this Connection ob-
ject
17 Get Production
Inhibit
Time
UINT Defines minimum time between new data pro-
ductin. This attribute is required for I/O Client
connection.
5. How to Access the Parameters FC 100/ 200/ 300 DeviceNet
42
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark