Operating instructions

5.3.10. Instance 4: Change of State/Cycle
Attrib-
ute
Access Name Data
type
Description
1 Get State USINT State of the object
2 Get Instance
Type
USINT Indicates either I/O or Explicit Message
3 Get Transport
Class Trig-
ger
USINT Defines behaviour of the connection
4 Get Produced
Connec-
tion ID
UINT CAN Identifier Field when the connection trans-
mits
5 Get Consumed
Connec-
tion ID
UINT CAN Identifier Field value that denotes message
to be received
6 Get Initial
Communi-
cation
Character-
istics
USINT Defines the message group(s) across which pro-
ductions and consumptions associated with this
connection occur
7 Get Produced
Connectin
size
UINT Maximum number of bytes transmitted across
this connection
8 Get Consumed
Connec-
tion size
UINT Maximum number of bytes received across this
connection
9 Get/Set Expected
Package
Rate
UINT Defines value used in Transmission Trigger Tim-
er and Inactivity/Watchdog timer
12 Get Watchdog
timeout
action
USINT Defines how to handle Inactivity/Watchdog
timeout
13 Get Produced
Connec-
tion Path
Length
UINT Number of Bytes in the produced connection
path attribute
14 Get Produced
Connecti-
no Path
Array of
USINT
Specifies the Application object(s) whose data is
to be produced by these Connection Objects
15 Get Consumd
Connec-
tion Path
Length
UINT Number of bytes in the consumed connection
path attribute
16 Get Consumed
Connec-
tion Path
Array of
USINT
Specifies the Application object(s) that are to re-
ceive the data consumed by this Connection ob-
ject
17 Get Production
Inhibit
Time
UINT Defines minimum time between new data pro-
ductin. This attribute is required for I/O Client
connection.
5.3.11. Class ID 0F4 Parameter Object
This object is an interface to the parameters of the drive. It identifies configurable parameters
and supplies their description, including min. and max. values and a descriptive text.
5. How to Access the Parameters FC 100/ 200/ 300 DeviceNet
44
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
5