6. Parameters
8-01 Control Site
Option: Function:
[0]
*
Digital and ctrl. word Control by using both digital input and control word.
[1] Digital only Control by using digital inputs only.
[2] Control word only Control by using control word only.
The setting in this parameter overrides the settings in par. 8-50 to 8-56.
8-02 Control Word Source
Option: Function:
[0] None
[1] FC RS485
[2] FC USB
[3] Option A
[4] Option B
[5] Option C0
[6] Option C1
[30] External Can Select the source of the control word: one of two serial interfa-
ces or four installed options. During initial power-up, the fre-
quency converter automatically sets this parameter to
Option
A
[3] if it detects a valid fieldbus option installed in slot A. If the
option is removed, the frequency converter detects a change in
the configuration, sets par. 8-02 back to default setting
FC
RS485
, and the frequency converter then trips. If an option is
installed after initial power-up, the setting of par. 8-02 will not
change but the frequency converter will trip and display: Alarm
67
Option Changed
.
This parameter cannot be adjusted while the motor is running.
8-03 Control Word Timeout Time
Range: Function:
1.0s
*
[0.1 - 18000.0 s] Enter the maximum time expected to pass between the recep-
tion of two consecutive telegrams. If this time is exceeded, it
indicates that the serial communication has stopped. The func-
tion selected in par. 8-04
Control Word Time-out Function
will
then be carried out. The time-out counter is triggered by a valid
control word.
8-04 Control Word Timeout Function
Option: Function:
[0]
*
Off
[1] Freeze Output
[2] Stop