Operating instructions

Select the control source in Instance 21/71 and 20-70.
[0]
*
Off Enables control via analog/digital inputs.
[1] On enable control via the fieldbus.
10-20 COS Filter 1
Range: Function:
0
*
[0 - FFFF] Sets up the filter mask for the status word. When operating in
COS (Change-Of-State), it is possible to filter out bits in the sta-
tus word that should not be sent if they change.
10-21 COS Filter 2
Range: Function:
65535
*
[0 - 65535] Sets up the filter mask for the Main Actual Value. When oper-
ating in COS (Change-Of-State), it is possible to filter out bits in
the Main actual value that should not be sent if they change.
10-22 COS Filter 3
Range: Function:
65535
*
[0 - 65535] Sets up the filter mask for PCD 3. When operating in COS
(Change-Of-State), it is possible to filter out bits in PCD 3 that
should not be sent if they change.
10-23 COS Filter 4
Range: Function:
65535
*
[0 - 65535] Sets up the filter mask for PCD 4. When operating in COS
(Change-Of-State), it is possible to filter out bits in PCD 4 that
should not be sent if they change.
10-30 Array Index
Range: Function:
0
*
[0 - 255] View array parameters. This parameter is valid only when a De-
viceNet fieldbus is installed.
10-31 Store Data Values
Option: Function:
[0]
*
Off
[1] Store edit set-up
[2] Store all set-ups This parameter is used to activate a function that stores all pa-
rameter values in the non-volatile memory thus retaining
changed parameter values at power down.
-
'*Off:
The store function is inactive.
-
Store edit set-up:
All parameter values in the set-up selected
will be stored in the non-volatile memory.
The value returns to
Off
when all values have been stored.