Operating instructions

Danfoss District Energy VI.SH.K1.02 DEN-SMT/PL
1
Instruction
1.0 Table of contents
SONO 1500 CT
Ultrasonic ow sensor
2.0 Safety notes and product information
1.0 Table of contents ......................................................................................................................................................................................................................................................................... 1
2.0 Safety notes and product information ........................................................................................................................................................................................................................1
3.0 Installation of ow sensor ..................................................................................................................................................................................................................................................... 2
4.0 Power supply .................................................................................................................................................................................................................................................................................. 3
5.0 Connection diagram ................................................................................................................................................................................................................................................................. 3
6.0 Wiring energy calculator type INFOCAL 8 ................................................................................................................................................................................................................. 4
7.0 Start-up operation ......................................................................................................................................................................................................................................................................4
8.0 Communication ...........................................................................................................................................................................................................................................................................4
Following instructions refer to the ultrasonic ow sensor.
The regulations on the use of energy meters must be observed! The
meter installation is only to be performed by an installation and/
or electrical contractor using personnel trained in the installation
and use of electrical equipment and familiar with the Low Voltage
Directive.
- Medium: water, as per AGFW Instruction Sheet FW510.If water
additives are used (e.g. corrosion protection), the user must
make sure that the corrosion resistance is adequate.
- The specied medium temperature
is 5 ... 90°C/105°C/130°C(150°C)
- The temperature range depends on variant and nominal size
- The exact temperature range is shown on the type plate
- The sealed variant is to be used if condensation is expected
- The specied operating/ambient conditions are:
5…55 °C; max. 93% rel. humidity
- IP54 (heating) / IP65 (cooling, heat/cooling)
- Ambient temperatures below 35 °C ensures typical battery
lifetime
This installation guide is intended for trained personnel and
does not contain any basic working steps.
If the ow sensor is insulated with the pipeline,
the calculator must be accessible.
Safety Note
The seal on the ow sensor must not be damaged!
A damaged seal will result in immediate invalidation
of the factory warranty and verication.
The relevant ESD regulations (electrostatic discharge)must be
observed.
No liability is accepted for damage (especially to electronic circuits)
resulting from failure to comply with the ESD regulations.