Brochure

For full data details, capacity tables or use with other
refrigerants, please refer to the Online Coolselector®2:
coolselector.danfoss.com
Danfoss Scrolls H, SH, DSH series
Data given for Code 4: 400V - 50 Hz
460V - 60 Hz : 3 phases.
Net weight with oil charge
TR = Ton of Refrigeration
COP = Coecient Of Performance,
400V / 3ph / 50Hz
EER = Energy Eciency Ratio,
460V / 3ph / 60Hz
ARI: evap. temp. 7.2 °C/45°F; cond. temp.
54.4 °C/130°F; superheat 11.1 K/20°F;
subcooling 8.3 K/15°F
EN12900: evap. temp. 5 °C/41°F; cond.
temp. 50 °C/122°F; superheat: 10 K/18°F;
subcooling: 0 K
Ready for
lower
GWP
refrigerants R452B
and R454B. Ongoing
qualication for R32.
R410A - 400V / 3 ~ / 50Hz
Model
Nominal cooling
capacity
50 Hz, EN12900 ratings 50 Hz, ARI ratings
Cooling capacity Eciency Cooling Capacity Eciency
TR - 60Hz W COP in W/W W COP in W/W
HRH029 2.4 6 300 2.86 7 100 2.93
HRH031 2.6 6 700 2.77 7 500 2.81
HRH032 2.7 6 800 2.77 7 700 2.78
HRH034 2.8 7 500 2.88 8 500 2.93
HRH036 3.0 7 800 2.79 8 800 2.81
HRH038 3.2 8 200 2.72 9 300 2.75
HRH040 3.3 9 000 2.79 10 200 2.84
HRH041 3.3 8 900 2.88 10 000 2.93
HRH044 3.7 9 600 2.77 10 800 2.75
HRH049 4.1 10 700 2.96 12 100 2.99
HRH051 4.3 11 400 3.01 12 900 3.05
HRH054 4.5 11 900 2.96 13 300 3.02
HRH056 4.7 12 300 2.98 13 800 3.02
HLH061 5.1 13 200 3.01 14 800 3.11
HLH068 5.7 15 000 3.11 16 900 3.21
HLJ072 6.0 15 800 3.11 17 800 3.21
HLJ075 6.3 16 500 3.12 18 600 3.22
HLJ083 6.9 18 200 3.13 20 400 3.25
DCJ091 7.5 19 600 3.09 22 100 3.16
DCJ106 8.8 23 000 3.12 25 800 3.18
DCJ121 10 26 250 3.11 29 300 3.14
DSH090 7.5 20 050 3.06 22 490 3.12
DSH105 9 23 580 3.08 26 460 3.15
DSH120 10 26 790 3.11 30 050 3.18
DSH140 12 30 370 3.13 34 100 3.20
DSH161 13 34 890 3.16 39 130 3.22
DSH184 15 39 040 3.16 43 710 3.22
DSH240 20 52 730 3.10 59 050 3.15
DSH295 25 64 520 3.17 72 240 3.22
DSH381 32 81 490 3.11 91 420 3.18
DSH485 40 103 530 3.16 116 420 3.25
DSH600* 50 128 860 3.18 144 560 3.23
* preliminary data
15Compressors for Commercial Air Conditioning