Technical data

VLT 5000/5000 FLUX SyncPos Quick-Setup
MG.10.Q1.5B – VLT is a registered Danfoss trade mark10
drive forward for example in local mode (Parameter
002 = ”Local”) then the position must count positive. If
the position is counting negative you must swap A and
B channels from the encoder or two motor phases.
You can also turn the encoder by hand (the motor
should not be connected!). The position is
continuously registered in the communications
window.
For a full rotation you should receive 4
times the value of the resolution of the encoder, that
means 2000 if the Encoder pulses per revolution is
500.
Ending the encoder check
End the test of the encoder with the
[ESC] key and
close the test program with "FILE"
"CLOSE".
A
successful test of the encoder is a requirement for
further starting up of operations.
If the encoder doesn’t work
If the VLT parameter 002 is "LOCAL" please change
it = "REMOTE". Click on "DEVELOPMENT" and
start the test program with "EXECUTE"
or
[F5].
The test is successful if the motor runs slowly back
and forth and position 500 is registered.
End the test with [ESC] and "CLOSE" the "FILE".
If the motor doesn’t move
This could be a result of incorrect cable installa-
tion.
Measure the signals coming from the
encoder and compare them to the values listed in
the specifications.
Check whether the connection
was made according to the application.
If the motor doesn’t move at all, then the propor-
tional factor of the PID filter is probably too low or
the VLT has not been enabled.
Another possibility
is that the encoder resolution is high. Therefore
we recommend to change line 17 "POSA500" to
be half the encoder resolution in quadcounts.
E.g. encoder ppr is 4096. Line 17 should be
changed to (4096 x 4/2) "POSA 8192".
Check the VLT enable (terminal 27 = 24 V) and
check that the VLT wasn't stopped via the LCP
(flashing display). Then increase the
ProportionalProportional
ProportionalProportional
Proportional
factor factor
factor factor
factor (parameter 702). (See following chart).
Execute the test run program
Now connect the motor to the VLT, make sure
that the motor can turn completely freely.
NB!
The motor must be provided with an
[EMERGENCY STOP] button.
NB!
Turn off the motor immediately with
the EMERGENCY STOP button if it
vibrates heavily or sets off uncontrolled.
Click on "FILE" and "OPEN"
the file
Move-S.m Move-S.m
Move-S.m Move-S.m
Move-S.m.
Encoder ppr (ENCODER) Proportional (KPROP) par 702
500 200
512 200
1000 100
1024 100
2000 50
2048 50
2500 50
3600 25
4096 25
5000 25
If the encoder is not mounted on the motor please
note the gear-ratio between motor and encoder.
Use this ratio to multiply the Proportional factor. E.g.
motor turns 2 rev. encoder turns 1 rev. ratio is 1:2.
Multiply the Proportional factor with 2.
If the motor vibrates heavily...
then you have to: reduce the
ProportionalProportional
ProportionalProportional
Proportional
factor factor
factor factor
factor KPROP (11). If the drive stops due to a O.
Err. 8 in the LCP" then it is necessary to increase
the
TT
TT
T
olerated position error olerated position error
olerated position error olerated position error
olerated position error POSERR (15). (See 10
steps to optimise the PID loop).
Checking encoder connections