Technical data

VLT 5000/5000 FLUX SyncPos Quick-Setup
MG.10.Q1.5B VLT is a registered Danfoss trade mark22
O.ERR_91
SyncPos
Curve array wrong
Meaning
An incorrect or old array is defined in the DIM
instruction for SETCURVE.
Tip
An old array may exist if the cnf file with all para-
meters and arrays has not been loaded into the
CAM-Editor.
An incorrect array could be caused by the
following:
It was not created by the curve editor.
Previous version of a curve editor. Such an ar-
ray must first be converted by the current
curve editor ( "LOAD" and "SAVE").
Or the order of the arrays in the DIM instruc-
tion does not match the order in the cnf file.
Refer to the number of the array in the title
bar of the CAM-Editor in this respect.
O.ERR_92
SyncPos
Error from encoder monitoring
Meaning
Open or short circuit in accordance with the dis-
played LED
NB!
An error will be indicated even if no encoder
is connected.
O.ERR_xx
SyncPos
Internal error ##
Meaning
If such an error should occur, please contact your
dealer and report the error number displayed to
the technical service department.
VLT software SyncPos messages
The VLT software SyncPos messages are arranged
in alphabetical order. Letters following a % sign
represent variables which can be used in plain text
at the corresponding locations.
Compilation error ...
SyncPos
Compilation error(s): program not saved!
Meaning and tip
A file is always compiled first and then saved. If
you want to save the program, for example in the
menu "CONTROLLER
"SAVE PROGRAM" and
a syntax error is found during compilation this
message will be displayed.
Start the SYNTAX CHECK in the menu
DEVELOPMENT, correct the syntax error and
then save the program.
Connection to ... already exists ...
SyncPos
Connection to %d already exists [%s] - change to
new Window?
Meaning
When opening a new window or when trying to
connect a window with a controller that is already
linked to a window.
Yes The controller is disconnected from the old
window and linked to the new window.
No The controller stays connected to the old
window, the new window is not linked to a
controller.
Controller is executing a program ...
SyncPos
Controller is executing a program or command!
Meaning
When the controller is executing a command or
program it is not available for additional com-
mands. You have to
"BREAK" the new com-
mand and restart it once the previous command
has been completely executed.
Error messages