Technical data

23
MG.10.Q1.5B VLT is a registered Danfoss trade mark
VLT 5000/5000 FLUX SyncPos Quick-Setup
Error in array ...
SyncPos
Error in array part of file.
Meaning
When re-saving a configuration ("CONTROLLER"
"PARAMETERS"
"RESTORE FROM FILE")
the computer recognizes that the data in the array
area is formatted incorrectly.
Cause
In order to be able to save a file, the following
conditions must be fulfilled:
Identical software versions
same configuration (e.g. same number of
axes)
In the case that arrays have already been in-
putted, these must match the ones that are to
be saved in terms of type and size.
Error in axis parameter ...
SyncPos
Error in axis parameter part of file.
Meaning
When re-saving a configuration ("CONTROLLER"
"PARAMETERS"
"RESTORE FROM FILE")
the computer recognizes that the data in the area
of the axis parameters is formatted incorrectly. The
parameter number and the sequence must be cor-
rect and numbering must be continuous.
Cause
In order to be able to save a file, the following
conditions must be fulfilled:
Identical software versions, that provides
same number and order of the parameters
same configuration (e.g. same number of
axes)
Error in global parameter ...
SyncPos
Error in global parameter part of file.
Meaning
When re-saving a configuration ("CONTROLLER"
"PARAMETERS"
"RESTORE FROM FILE")
the computer recognizes that the data in the area
of the global parameters is formatted incorrectly.
Causes
In order to be able to save a file, the following
conditions must be fulfilled:
Identical software versions, that provides
same number and order of the parameters
same configuration (e.g. same number of
axes)
Lost connection to ...
SyncPos
Lost connection to #%d!
Meaning
If the VLT is turned off or the plug is pulled, etc.
the window is disconnected from the VLT and the
lost connection is registered.
Timeout: no reply from VLT
SyncPos
Timeout: no reply from VLT
Meaning
The VLT does not answer; check the connection.
Error messages