Operating instructions

VLT
®
2800, VLT
®
6000 HVAC and VLT
®
8000 AQUA Modbus RTU
Safety - Modbus
RTU
VLT 8000 AQUA
176FA159.12
Warning:
Touching the electrical parts may be fatal - even after the equipment has
been disconnected from line.
VLT 8006-8062, 200-240 V: wait at least 15 minutes
VLT 8006-8072, 380-480 V: wait at least 15 minutes
VLT 8102-8352, 380-480 V: wait at least 20 minutes
VLT 8450-8600, 380-480 V: wait at least 15 minutes
VLT 8002-8006, 525-600 V: wait at least 4 minutes
VLT 8008-8027, 525-600 V: wait at least 15 minutes
VLT 8032-8300, 525-600 V: wait at least 30 minutes
MG.10.S2.02 - VLT is a registered Danfoss trademark