Specifications

2.7 Control Structures
2.7.1 Control Principle
1-00 Configuration Mode can be selected if open or closed loop is to be used.
2.7.2 Control Structure Open Loop
130BB892.10
100%
0%
-100%
100%
Local
reference
scaled to
Hz
Auto mode
Hand mode
LCP Hand on,
off and auto
on keys
Local
Remote
Reference
Ramp
P 4-10
Motor speed
direction
To motor
control
Reference
handling
Remote
reference
P 4-14
Motor speed
high limit [Hz]
P 4-12
Motor speed
low limit [Hz]
P 3-4* Ramp 1
P 3-5* Ramp 2
Illustration 2.17 Open Loop Structure
In the configuration shown in Illustration 2.17, 1-00 Configu-
ration Mode is set to [0] Open loop. The resulting reference
from the reference handling system or the local reference
is received and fed through the ramp limitation and speed
limitation before being sent to the motor control. The
output from the motor control is then limited by the
maximum frequency limit.
2.7.3 PM/EC+ Motor Control
The Danfoss EC+ concept provides the possibitily for using
high efficient PM motors (permanent magnet motors) in
IEC standard frame size operated by Danfoss frequency
converters.
The commissioning procedure is comparable to the
existing one for asynchronous (induction) motors by
utilising the Danfoss VVC
plus
PM control strategy.
Customer advantages:
Free choice of motor technology (permanent
magnet or induction motor)
Installation and operation as know on induction
motors
Manufacturer independent when selecting system
components (e.g. motors)
Best system efficiency by selecting best
components
Possible retrofit of existing installations
Power range: 45 kW (200 V), 0.37-90 kW (400 V),
90 kW (600 V) for induction motors and 0.37-22
kW (400 V) for PM motors.
Current limitations for PM motors:
Currently only supported up to 22 kW
Currently limited to non salient type PM motors
LC filters not supported together with PM motors
Over Voltage Control algorithm is not supported
with PM motors
Kinetic backup algorithm is not supported with
PM motors
Support reduced AMA of the stator resistance Rs
in the system only
No stall detection
No ETR function
Product Overview
VLT
®
HVAC Basic Drive FC 101 Design Guide
MG18C502 - Rev. 2013-09-06 25
2 2