Specifications

Closed Loop Set-up Wizard
Parameter Range Default Function
0-03 Regional Settings [0] International
[1] US
0
0-06 GridType [0] -[[132] see start -up wizard
for open loop application
Size selected Select operating mode for restart upon
reconnection of the frequency converter to
mains voltage after power down
1-00 Configuration Mode [0] Open loop
[3] Closed loop
0 Change this parameter to Closed loop
1-10 Motor Construction *[0] Motor construction
[1] PM, non salient SPM
[0] Asynchron Setting the parameter value might change
these parameters:
1-01 Motor Control Principle
1-03 Torque Characteristics
1-14 Damping Gain
1-15 Low Speed Filter Time Const
1-16 High Speed Filter Time Const
1-17 Voltage filter time const
1-20 Motor Power
1-22 Motor Voltage
1-23 Motor Frequency
1-25 Motor Nominal Speed
1-26 Motor Cont. Rated Torque
1-30 Stator Resistance (Rs)
1-33 Stator Leakage Reactance (X1)
1-35 Main Reactance (Xh)
1-37 d-axis Inductance (Ld)
1-39 Motor Poles
1-40 Back EMF at 1000 RPM
1-66 Min. Current at Low Speed
1-72 Start Function
1-73 Flying Start
4-19 Max Output Frequency
4-58 Missing Motor Phase Function
1-20 Motor Power
0.09-110 kW Size related Enter motor power from nameplate data
1-22 Motor Voltage 50.0-1000.0 V Size related Enter motor voltage from nameplate data
1-23 Motor Frequency 20.0-400.0 Hz Size related Enter motor frequency from nameplate data
1-24 Motor Current 0.0 -10000.00 A Size related Enter motor current from nameplate data
1-25 Motor Nominal Speed 100.0-9999.0 RPM Size related Enter motor nominal speed from nameplate
data
1-26 Motor Cont. Rated Torque 0.1-1000.0 Size relate This parameter is available only when
1-10 Motor Construction Design is set to [1]
PM, non-salient SPM.
NOTICE
Changing this parameter affects
settings of other parameters
1-29 Automatic Motor Adaption
(AMA)
Off Performing an AMA optimizes motor
performance
1-30 Stator Resistance (Rs) 0.000-99.990 Size related Set the stator resistance value
1-37 d-axis Inductance (Ld) 0-1000 Size related Enter the value of the d-axis inductance.
Obtain the value from the permanent magnet
motor data sheet. The de-axis inductance
cannot be found by performing an AMA.
1-39 Motor Poles 2-100 4 Enter the number of motor poles
1-40 Back EMF at 1000 RPM 10-9000 Size related Line-Line RMS back EMF voltage at 1000 RPM
How to Programme
VLT
®
HVAC Basic Drive FC 101 Design Guide
MG18C502 - Rev. 2013-09-06 75
6 6