Specifications

Parameter Range Default Function
1-73 Flying Start [0] Disabled
[1] Enabled
0
Select [1] Enable to enable the frequency
converter to catch a spinning motor. I.e. fan
applications. When PM is selected, Flying Start
is enabled.
3-02 Minimum Reference -4999-4999 0 The minimum reference is the lowest value
obtainable by summing all references
3-03 Maximum Reference -4999-4999 50 The maximum reference is the highest value
obtainable by summing all references
3-10 Preset Reference -100-100% 0 Enter the set point
3-41 Ramp 1 Ramp Up Time 0.05-3600.0 s Size related
Ramp up time from 0 to rated 1-23 Motor
Frequency if Asynchron motor is selected;
ramp up time from 0 to 1-25 Motor Nominal
Speed if PM motor is selected"
3-42 Ramp 1 Ramp Down Time 0.05-3600.0 s Size related
Ramp down time from rated 1-23 Motor
Frequency to 0 if Asynchron motor is selected;
ramp down time from 1-25 Motor Nominal
Speed to 0 if PM motor is selected
4-12 Motor Speed Low Limit [Hz] 0.0-400 Hz 0.0 Hz Enter the minimum limit for low speed
4-14 Motor Speed High Limit [Hz] 0-400 Hz 65 Hz Enter the minimum limit for high speed
4-19 Max Output Frequency 0-400 Size related Enter the maximum output frequency value
6-29 Terminal 54 mode [0] Current
[1] Voltage
1 Select if terminal 54 is used for current- or
voltage input
6-20 Terminal 54 Low Voltage 0-10 V 0.07 V Enter the voltage that corresponds to the low
reference value
6-21 Terminal 54 High Voltage 0-10 V 10 V Enter the voltage that corresponds to the low
high reference value
6-22 Terminal 54 Low Current 0-20 mA 4 Enter the current that corresponds to the high
reference value
6-23 Terminal 54 High Current 0-20 mA 20 Enter the current that corresponds to the high
reference value
6-24 Terminal 54 Low Ref./Feedb.
Value
-4999-4999 0 Enter the feedback value that corresponds to
the voltage or current set in 6-20 Terminal 54
Low Voltage/6-22 Terminal 54 Low Current
6-25 Terminal 54 High Ref./Feedb.
Value
-4999-4999 50 Enter the feedback value that corresponds to
the voltage or current set in 6-21 Terminal 54
High Voltage/6-23 Terminal 54 High Current
6-26 Terminal 54 Filter Time
Constant
0-10 s 0.01 Enter the filter time comstant
20-81 PI Normal/ Inverse Control [0] Normal
[1] Inverse
0
Select [0] Normal to set the process control to
increase the output speed when the process
error is positive. Select [1] Inverse to reduce
the output speed.
20-83 PI Start Speed [Hz] 0-200 Hz 0 Enter the motor speed to be attained as a
start signal for commencement of PI control
20-93 PI Proportional Gain 0-10 0.01 Enter the process controller proportional gain.
Quick control is obtained at high amplifi-
cation. However if amplification is too great,
the process may become unstable
20-94 PI Integral Time 0.1-999.0 s 999.0 s Enter the process controller integral time.
Obtain quick control through a short integral
time, though if the integral time is too short,
the process becomes unstable. An excessively
long integral time disables the integral action.
Table 6.5 Closed Loop Application
How to Programme
VLT
®
HVAC Basic Drive FC 101 Design Guide
76 MG18C502 - Rev. 2013-09-06