Specifications

Motor Set-up
The Quick Menu Motor Set-up guides through the needed motor parameters.
Parameter Range Default Function
0-03 Regional Settings [0] International
[1] US
0
0-06 GridType [0] -[132] see start -up wizard for
open loop application
Size selected Select operating mode for restart
upon reconnection of the frequency
converter to mains voltage after
power down
1-10 Motor Construction *[0] Motor construction
[1] PM, non salient SPM
[0] Asynchron
1-20 Motor Power 0.12-110 kW/0.16-150 hp Size related Enter motor power from nameplate
data
1-22 Motor Voltage 50.0-1000.0 V Size related Enter motor voltage from nameplate
data
1-23 Motor Frequency 20.0-400.0 Hz Size related Enter motor frequency from
nameplate data
1-24 Motor Current 0.01-10000.00 A Size related Enter motor current from nameplate
data
1-25 Motor Nominal Speed 100.0-9999.0 RPM Size related Enter motor nominal speed from
nameplate data
1-26 Motor Cont. Rated Torque 0.1-1000.0 Size related This parameter is available only when
1-10 Motor Construction Design is set
to [1] PM, non-salient SPM.
NOTICE
Changing this parameter affects
settings of other parameters
1-30 Stator Resistance (Rs) 0.000-99.990 Size related Set the stator resistance value
1-37 d-axis Inductance (Ld) 0-1000 Size related Enter the value of the d-axis
inductance.
Obtain the value from the permanent
magnet motor data sheet. The de-axis
inductance cannot be found by
performing an AMA.
1-39 Motor Poles 2-100 4 Enter the number of motor poles
1-40 Back EMF at 1000 RPM 10-9000 Size related Line-Line RMS back EMF voltage at
1000 RPM
1-73 Flying Start [0] Disabled
[1] Enabled
0
Select [1] Enable to enable the
frequency converter to catch a
spinning motor
3-41 Ramp 1 Ramp Up Time 0.05-3600.0 s Size related Ramp up time from 0 to rated
1-23 Motor Frequency
3-42 Ramp 1 Ramp Down Time 0.05-3600.0 s Size related Ramp down time from rated
1-23 Motor Frequency to 0
4-12 Motor Speed Low Limit
[Hz]
0.0-400 Hz 0.0 Hz Enter the minimum limit for low
speed
4-14 Motor Speed High Limit
[Hz]
0.0-400 Hz 65 Enter the maximum limit for high
speed
4-19 Max Output Frequency 0-400 Size related Enter the maximum output frequency
value
Table 6.6 Motor Parameters
How to Programme
VLT
®
HVAC Basic Drive FC 101 Design Guide
MG18C502 - Rev. 2013-09-06 77