Specifications

Changes Made
Changes Made lists all parameters changed since factory
setting. Only the changed parameters in current edit-setup
are listed in changes made.
If the parameter's value is changed back to factory
setting's value from another different value, the parameter
will NOT be listed in Changes Made.
1. Press [Menu] to enter the Quick Menu until
indicator in display is placed above Quick Menu.
2.
Press [
] [
] to select either wizard, closed loop
setup, motor setup or changes made, then press
[OK].
3.
Press [
] [
] to browse through the parameters
in the Quick Menu.
4. Press [OK] to select a parameter.
5.
Press [
] [
] to change the value of a parameter
setting.
6. Press [OK] to accept the change.
7. Press either [Back] twice to enter “Status”, or
press [Menu] once to enter “Main Menu”.
6.3.4
Main Menu
[Main Menu] is used for access to and programming of all
parameters. The Main Menu parameters can be accessed
readily unless a password has been created via 0-60 Main
Menu Password.
For the majority of VLT
®
HVAC Basic Drive applications it is
not necessary to access the Main Menu parameters but
instead the Quick Menu provides the simplest and quickest
access to the typical required parameters.
The Main Menu accesses all parameters.
1. Press [Menu] until indicator in display is placed
above “Main Menu”.
2.
Press [
] [
] to browse through the parameter
groups.
3. Press [OK] to select a parameter group.
4.
Press [
] [
] to browse through the parameters
in the specific group.
5. Press [OK] to select the parameter.
6.
Press [
] [
] to set/change the parameter value.
Press [Back] to go back one level.
6.4
Quick Transfer of Parameter Settings
between Multiple Frequency Converters
Once the set-up of a frequency converter is complete,
Danfoss recommends to store the data in the LCP or on a
PC via MCT 10 Set-up Software tool.
Data transfer from frequency converter to LCP:
WARNING
Stop the motor before performing this operation.
1.
Go to 0-50 LCP Copy
2. Press [OK]
3.
Select [1] All to LCP
4. Press [OK]
Connect the LCP to another frequency converter and copy
the parameter settings to this frequency converter as well.
Data transfer from LCP to frequency converter:
WARNING
Stop the motor before performing this operation.
1.
Go to 0-50 LCP Copy
2. Press [OK]
3.
Select [2] All from LCP
4. Press [OK]
6.5
Read-out and Programming of Indexed
Parameters
Select the parameter, press [OK], and press [
]/[
] to scroll
through the indexed values. To change the parameter
value, select the indexed value and press [OK]. Change the
value by pressing [
]/[
]. Press [OK] to accept the new
setting. Press [Cancel] to abort. Press [Back] to leave the
parameter.
6.6
Initialise the Frequency Converter to
Default Settings in two Ways
Recommended initialisation (via 14-22 Operation Mode)
1.
Select 14-22 Operation Mode.
2. Press [OK].
3.
Select [2] Initialisation and Press [OK].
4. Cut off the mains supply and wait until the
display turns off.