Specifications

7 RS-485 Installation and Set-up
7.1 RS-485
7.1.1 Overview
RS-485 is a 2-wire bus interface compatible with multi-drop
network topology, that is, nodes can be connected as a
bus, or via drop cables from a common trunk line. A total
of 32 nodes can be connected to one network segment.
Repeaters divide network segments.
NOTICE
Each repeater functions as a node within the segment in
which it is installed. Each node connected within a given
network must have a unique node address, across all
segments.
Terminate each segment at both ends, using either the
termination switch (S801) of the frequency converters or a
biased termination resistor network. Always use screened
twisted pair (STP) cable for bus cabling, and always follow
good common installation practice.
Low-impedance earth connection of the screen at every
node is important, including at high frequencies. Thus,
connect a large surface of the screen to earth, for example
with a cable clamp or a conductive cable gland. It may be
necessary to apply potential-equalizing cables to maintain
the same earth potential throughout the network - partic-
ularly in installations with long cables.
To prevent impedance mismatch, always use the same
type of cable throughout the entire network. When
connecting a motor to the frequency converter, always use
screened motor cable.
Cable Screened twisted pair (STP)
Impedance
[Ω]
120
Cable length
[m]
Max. 1200 (including drop lines)
Max. 500 station-to-station
Table 7.1 Cable
7.1.2
Network Connection
Connect the frequency converter to the RS-485 network
as follows (see also Illustration 7.1):
1. Connect signal wires to terminal 68 (P+) and
terminal 69 (N-) on the main control board of the
frequency converter.
2. Connect the cable screen to the cable clamps.
NOTICE
Screened, twisted-pair cables are recommended
to reduce noise between conductors.
61 68 69
N
P
COMM. GND
130BB795.10
Illustration 7.1 Network Connection
7.1.3 Frequency Converter Hardware Set-
up
Use the terminator dip switch on the main control board
of the frequency converter to terminate the RS-485 bus.
130BB966.10
Illustration 7.2 Terminator Switch Factory Setting
The factory setting for the dip switch is OFF.
RS-485 Installation and Set...
VLT
®
HVAC Basic Drive FC 101 Design Guide
80 MG18C502 - Rev. 2013-09-06