Specifications

7.11.2 Status Word According to FC Profile
(STW) (8-30 Protocol = FC profile)
Output freq.STW
Bit
no.:
Follower-master
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BA273.11
Illustration 7.14 Status Word
Bit Bit=0 Bit=1
00 Control not ready Control ready
01 Drive not ready Drive ready
02 Coasting Enable
03 No error Trip
04 No error Error (no trip)
05 Reserved -
06 No error Triplock
07 No warning Warning
08
Speed reference
Speed=reference
09 Local operation Bus control
10 Out of frequency limit Frequency limit OK
11 No operation In operation
12 Drive OK Stopped, auto start
13 Voltage OK Voltage exceeded
14 Torque OK Torque exceeded
15 Timer OK Timer exceeded
Table 7.35 Status Word According to FC Profile
Explanation of the status bits
Bit 00, Control not ready/ready
Bit 00=’0’: The frequency converter trips.
Bit 00=’1’: The frequency converter controls are ready but
the power component does not necessarily receive any
power supply (in case of external 24 V supply to controls).
Bit 01, Drive ready
Bit 01=’0’: The frequency converter is not ready.
Bit 01=’1’: The frequency converter is ready for operation
but the coasting command is active via the digital inputs
or via serial communication.
Bit 02, Coasting stop
Bit 02=’0’: The frequency converter releases the motor.
Bit 02=’1’: The frequency converter starts the motor with a
start command.
Bit 03, No error/trip
Bit 03=’0’ : The frequency converter is not in fault mode.
Bit 03=’1’: The frequency converter trips. To re-establish
operation, press [Reset].
Bit 04, No error/error (no trip)
Bit 04=’0’: The frequency converter is not in fault mode. Bit
04=“1”: The frequency converter shows an error but does
not trip.
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error / triplock
Bit 06=’0’: The frequency converter is not in fault mode. Bit
06=“1”: The frequency converter is tripped and locked.
Bit 07, No warning/warning
Bit 07=’0’: There are no warnings.
Bit 07=’1’: A warning has occurred.
Bit 08, Speed reference/speed=reference
Bit 08=’0’: The motor is running but the present speed is
different from the preset speed reference. It might for
example, be the case when the speed ramps up/down
during start/stop.
Bit 08=’1’: The motor speed matches the preset speed
reference.
Bit 09, Local operation/bus control
Bit 09=’0’: [Off/Reset] is activate on the control unit or
Local control in 3-13 Reference Site is selected. It is not
possible to control the frequency converter via serial
communication.
Bit 09=’1’ It is possible to control the frequency converter
via the fieldbus/serial communication.
Bit 10, Out of frequency limit
Bit 10=’0’: The output frequency has reached the value in
4-12 Motor Speed Low Limit [Hz] or 4-14 Motor Speed High
Limit [Hz].
Bit 10="1": The output frequency is within the defined
limits.
Bit 11, No operation/in operation
Bit 11=’0’: The motor is not running.
Bit 11=’1’: The coasting has a start signal or the output
frequency is greater than 0 Hz.
Bit 12, Drive OK/stopped, autostart
Bit 12='0’: There is no temporary over temperature on the
inverter.
Bit 12=’1’: The inverter stops because of over temperature
but the unit does not trip and resumes operation once the
over temperature stops.
Bit 13, Voltage OK/limit exceeded
Bit 13=’0’: There are no voltage warnings.
Bit 13=’1’: The DC voltage in the frequency converter’s
intermediate circuit is too low or too high.
Bit 14, Torque OK/limit exceeded
Bit 14=’0’: The motor current is lower than the torque limit
selected in 4-18 Current Limit.
Bit 14=’1’: The torque limit in 4-18 Current Limit is
exceeded.
RS-485 Installation and Set...
VLT
®
HVAC Basic Drive FC 101 Design Guide
96 MG18C502 - Rev. 2013-09-06
77