Operating instructions

Issue 10/06 6 Commissioning
MICROMASTER 430
Operating Instructions (Compact)
23
6 Commissioning
6.1 Quick commissioning
The frequency inverter is adapted to the motor using the quick commissioning
function and important technological parameters are set. The quick commissioning
shouldn't be carried-out if the rated motor data saved in the frequency inverter
(4-pole 1LA Siemens motor, star circuit configuration
frequency inverter (FU)-
specific) match the rating plate data.
Parameters, designated with a * offer more setting possibilities than are actually
listed here. Refer to the parameter list for additional setting possibilities.
Factory setting
P0003 = 3
User access level *
1 Standard: Allows access into most frequently used parameters
2 Extended: Allows extended access e.g. to inverter I/O functions
3 Expert (For expert use only)
Parameter filter *
0 All parameters
2 Inverter
3 Motor
4 Speed sensor
P0010 = 1
Commissioning parameter *
0 Ready
1 Quick commissioning
30 Factory setting
NOTE
P0010 should be set to 1 in order to parameterize the data of the motor rating
plate.
P0100 =...
Europe/ North America
(enters the line supply frequency)
0 Europe [kW], frequency default 50 Hz
1 North America [hp], frequency default 60 Hz
2 North America [kW], frequency default 60 Hz
NOTE
For P0100 = 0 or 1, the setting of switch DIP50/60 determines the value of
P0100.
OFF = kW, 50 Hz
ON = hp, 60 Hz
Select motor type
1 Asynchronous motor (induction motor)
2 Synchronous motor
NOTE
For P0300 = 2 (synchronous motor), only the V/f control types (P1300 < 20) are
permitted.
P0100 = 1, 2
P0100 = 0
START
P0004 = 0
0
1
P0300 =...
P0300 =...
1
0
0