Operating instructions

6 Commissioning Issue 10/06
MICROMASTER 430
30 Operating Instructions (Compact)
6.3.4 Digital outputs (DOUT)
BI: Function of digital output 1 *
Defines source of digital output 1.
BI: Function of digital output 2 *
Defines source of digital output 2.
BI: Function of digital output 3 *
Defines source of digital output 3.
CO/BO: State of digital outputs
Displays status of digital outputs (also
includes inversion of digital outputs via
P0748).
Invert digital output
Defines high and low states of relay for a
given function.
Common Settings: Closed
52.0 Drive ready 0
52.1 Drive ready to run 0
52.2 Drive running 0
52.3 Drive fault active 0
52.4 OFF2 active 1
52.5 OFF3 active 1
52.6 Switch on inhibit active 0
52.7 Drive warning active 0
52.8 Deviation setpoint/actual value 1
52.9 PZD control (Process Data Control) 0
52.A Maximum frequency reached 0
52.B Warning: Motor current limit 1
52.C Motor holding brake (MHB) active 0
52.D Motor overload 1
52.E Motor running direction right 0
52.F Inverter overload 1
53.0 DC brake active 0
53.1 Act. freq. f_act > P2167 (f_off) 0
53.2 Act. freq. f_act <= P1080 (f_min) 0
53.3 Act. current r0027 > P2170 0
53.4 Act. freq. f_act > P2155 (f_1) 0
53.5 Act. freq. f_act <= P2155 (f_1) 0
53.6 Act. freq. f_act >= setpoint 0
53.7 Act. Vdc r0026 < P2172 0
53.8 Act. Vdc r0026 > P2172 0
53.A PID output
r2294 == P2292 (PID_min) 0
53.B PID output
r2294 == P2291 (PID_max) 0
(52:3)
BI: Fct. of DOUT 1
P0731.C
-1
0
1
Invert DOUTs
0 ... 7
P0748 (0)
CO/BO: State DOUTs
r0747
r0747
Kl.20
Kl.18
.0
Function
xxxx.y
rxxxx.y
P0731 = xxxx.y
DOUT channel
Relay :
DC 30 V / 5 A
AC 250 V / 2 A
Kl.28
Kl.9
int. 24 V
max. 100 mA
NO
COM
NC
Kl.19
or
max. load capability
max. opening / closing time
5 / 10 ms
52.3
0
P0731 = ...
52.7
0.0
P0748 = ...
P0733 = ...
P0732 = ...
r0747 = ...