6.3.12 Inverter protection
Inverter overload reaction
Selects reaction of inverter to an internal over-temperature.
0 Reduce output frequency
1 Trip (F0004)
2 Reduce pulse frequency and output frequency
3 Reduce pulse frequency then trip (F0004)
A0504
A0505
A0506
F0004
F0005
Inverter overload reaction
P0290
f_pulse
control
i_max
control
r0036
r0037
Heat sink
temperature
P0292
IGBT
temperature
P0292
i
2
t
P0294
Inverter monitoring
P0292 =...
Inverter temperature warning
Defines the temperature difference (in ºC) between the overtemperature trip threshold and
the warning threshold of the inverter. The trip threshold is stored internally by the inverter
and cannot be changed by the user.
trip
T = T
warn
- P0292
trip
Temperature MM430, Frame Size
IGBT
110 °C
140 °C
95 °C
145 °C
90 °C
145 °C
CD - EF
Heat sink
warn
:
:
Temperature warning threshold of inverter T
Temperature shutdown threshold of inverter T
Delay, fan shutdown
This defines the delay time in seconds between powering down the frequency inverter and
then powering-down the fan. A setting of 0 means that the fan is immediately shut down
(powered-down).
0 s
P0295 = ...
P0290 = ...
0
15 °C