Operating instructions

6 Commissioning Issue 10/06
MICROMASTER 430
44 Operating Instructions (Compact)
6.3.16.3 Holding brake
¾ Series / commissioning for hazardous loads
lower the load to the floor
when replacing the frequency inverter, prevent (inhibit) the frequency
inverter from controlling the motor holding brake (MHB)
secure the load or inhibit the motor holding brake control (so that the brake
cannot be controlled) and then – and only then – carry-out quick
commissioning / parameter download using the PC-based tool (STARTER)
¾ Parameterize the weight equalization for hoisting gear applications
magnetizing time P0346 greater than zero
min. frequency P1080 should approximately correspond to the motor slip
r0330 (P1080 r0330)
Adapt the voltage boost to the load (P1310, P1311)
¾ It is not sufficient to just select the status signal r0052 bit 12 "motor holding
brake active" in P0731 – P0733. In order to activate the motor holding brake, in
addition, parameter P1215 must be set to 1.
¾ It is not permissible to use the motor holding brake as operating brake. The
reason for this is that the brake is generally only dimensioned/designed for a
limited number of emergency braking operations.
¾ The brake closing / opening times can be taken from the appropriate manual.
The following typical values have been taken from Motor Catalog M11
2003/2004, Page 2/51:
Motor size Brake type Opening time [ms] Closing time [ms]
63 2LM8 005-1NAxx 25 56
71 2LM8 005-2NAxx 25 56
80 2LM8 010-3NAxx 26 70
90 2LM8 020-4NAxx 37 90
100 2LM8 040-5NAxx 43 140
112 2LM8 060-6NAxx 60 210
132 2LM8 100-7NAxx 50 270
160 2LM8 260-8NAxx 165 340
180 2LM8 315-0NAxx 152 410
200
225
2LM8 400-0NAxx 230 390
Holding brake enable
Enables/disables holding brake function (MHB).
0 Motor holding brake disabled
1 Motor holding brake enabled
NOTE
The following must apply when controlling the brake relay via a digital output: P0731 = 52.C
(= 52.12) (refer to Section 6.3.4 "Digital outputs (DOUT)").
0
P1215 =...