6.3.17 Data sets
For many applications, it is advantageous, if several parameter settings can be
simultaneously changed during operation or during operational readiness using an
external signal. By using indexing, different settings can be saved under one
parameter. These are then activated when the data set is changed-over. The
following data sets are available:
¾ CDS Command Data Set
¾ DDS Drive Data Set
The “Hand/Auto” mode (refer to Chapter 5)) is a sub-set of the command data set.
6.3.17.1 Command data set (Local/Remote)
P0718 =...
CO/BO: Hand / Auto
0 automatic mode - i.e. the control (open-loop) via analog and digital inputs
1 manual mode – i.e. control via the BOP-2
This parameter can be modified using the “Hand/Auto” buttons on the BOP-2.
0
1
t
r0019
Bit12
Local
0
1
t
r0019
Bit15
Auto
0
1
t
P0718
Default: P0810 = 718:0
P0718 = 0 : P0700[0] = 2
P1000[0] = 2
Local/Auto
CDS1/CDS2
(Terminal)
P0718 = 1 : P0700[1] = 1
P1000[1] = 1
(MOP)
(BOP)
(ADC)
Local
Auto
P0810 =...
Command data set CDS bit 0 (local / remote)
Selects the command source in which bit 0 should be read-out to select a command data
set (CDS).
t0
1
2
3
(0:0)
BI: CDS b0 loc/rem
P0810
(0:0)
BI: CDS bit 1
P0811
t0
1
2
3
CO/BO: Act CtrlWd2
r0055
r0055
CO/BO: Act CtrlWd1
r0054
r0054
.15
.15
.15
.15
r0050
Active CDS
Selecting CDS
approx. 4 ms approx. 4 ms
r0050
CO: Active CDS
Changeover timeChangeover time
The currently active command data set (CDS) is displayed using parameter r0050.
P0811 =...
BI: CDS bit 1
Selects command source from which to read Bit 1 for selecting a command data set
(see P0810).
0
0
0:0