Operating instructions

6 Commissioning Issue 10/06
MICROMASTER 430
62 Operating Instructions (Compact)
Example:
1. Commissioning steps with a motor:
Carry-out commissioning at DDS1.
Connect P0820 (P0821 if required) to the DDS changeover source
(e.g. using DIN 4: P0704[0] = 99, P0820 = 722.3).
Copy DDS1 to DDS2 (P0819[0] = 0, P0819[1] = 1, P0819[2] = 2).
Adapt DDS2 parameters
(e.g. ramp-up / ramp-down times P1120[1] and P1121[1]).
DIN
ADC
P0820 = 722.3
SUM
setpoint
Sequence control
DIN4
AFM RFG
Motor
control
0
1
P1120
P1121
[0]
DDS1
[1]
DDS2
[2]
DDS3
M
Gating unit
2. Commissioning steps with 2 motors (motor 1, motor 2):
Commission motor 1; adapt the remaining DDS1 parameters.
Connect P0820 (P0821 if required) to the DDS changeover source
(e.g. via DIN 4: P0704[0] = 99, P0820 = 722.3).
Changeover to DDS2 (check using r0051).
Commission motor 2; adapt the remaining DDS2 parameters.
MM4
M1
K1
M2
K2
Motor 1
Motor 2