6.3.18 Diagnostic parameters
r0021
CO: Act. filtered frequency
Displays actual inverter output frequency (r0021) excluding slip compensation, resonance
damping and frequency limitation.
r0022
Act. filtered rotor speed
Displays calculated rotor speed based on inverter output frequency [Hz] x 120 / number of
poles.
r0313
60
[Hz] r0021 [1/min] r0022 =
r0032
CO: Act. filtered power
Displays motor power (power output at the motor shaft).
Motor
ω, M
M f 2 M P
mech π=ω=
[Nm] r0031 [1/min]
60
r0022
π 2
1000
1
[kW] r0032 =
[kW] r0032 0.75 [hp] r0032 =
r0035
CO: Motor temperature
Displays the measured motor temperature in °C.
r0036
CO: Frequency inverter utilization
Displays the frequency inverter utilization as a % referred to the overload. In so doing, the
value is calculated using the I
2
t model.
The I
2
t actual value relative to the maximum possible I
2
t value provides the level of
utilization.
r0039
CO: Energy consumpt. meter [kWh]
Displays electrical energy used by inverter since display was last reset.
ist
dtcosiu3dt
P
r0039
00
W
ϕ
=
=
ist
tt
r0052
CO/BO: Act. status word 1
Displays the first active status word (ZSW) of the frequency inverter (bit format) and can be
used to diagnose the inverter status.
Bit00 Drive ready 0 NO 1 YES
Bit01 Drive ready to run 0 NO 1 YES
Bit02 Drive running 0 NO 1 YES
Bit03 Drive fault active 0 NO 1 YES
Bit04 OFF2 active 0 YES 1 NO
Bit05 OFF3 active 0 YES 1 NO
Bit06 ON inhibit active 0 NO 1 YES
Bit07 Drive warning active 0 NO 1 YES
Bit08 Deviation setpoint / act. value 0 YES 1 NO
Bit09 PZD control 0 NO 1 YES
Bit10 Maximum frequency reached 0 NO 1 YES
Bit11 Warning: Motor current limit 0 YES 1 NO
Bit12 Motor holding brake active 0 NO 1 YES
Bit13 Motor overload 0 YES 1 NO
Bit14 Motor runs right 0 NO 1 YES
Bit15 Inverter overload 0 YES 1 NO