Operating instructions

6 Commissioning Issue 10/06
MICROMASTER 430
64 Operating Instructions (Compact)
r0054
CO/BO: Control word 1
Displays the first control word (STW) of the frequency inverter and can be used to display
the active commands.
Bit00 ON/OFF1 0 NO 1 YES
Bit01 OFF2: Electrical stop 0 YES 1 NO
Bit02 OFF3: Fast stop 0 YES 1 NO
Bit03 Pulse enable 0 NO 1 YES
Bit04 RFG enable 0 NO 1 YES
Bit05 RFG start 0 NO 1 YES
Bit06 Setpoint enable 0 NO 1 YES
Bit07 Fault acknowledge 0 NO 1 YES
Bit10 Control from PLC 0 NO 1 YES
Bit11 Reverse (setpoint inversion) 0 NO 1 YES
Bit13 Motor potentiometer MOP up 0 NO 1 YES
Bit14 Motor potentiometer MOP down 0 NO 1 YES
Bit15 CDS Bit 0 (Local/Remote) 0 NO 1 YES
r0063
CO: Actual frequency
Displays the actual frequency in Hz.
V/f
0
1,2
Encoder
P0400
160 ms
Act. frequencies:
Act. filtered frequency
Act. frequency
Act. encoder frequency
0
P0408 60
r0313
Act. filtered speed
r0313
60
r0022
r0021
r0063
r0061
r0067
CO: Act. output current limit
Displays valid maximum output current of inverter.
Motor
Inverter
Motor protection
P0640
r0067
P0305
Inverter protection
r0209
Min
r1114
CO: Freq. setpoint after dir. ctrl.
Displays the setpoint (reference) frequency in Hz after the function block to reverse the
direction of rotation.
r1170
CO: : Frequency setpoint after RFG
Displays the total frequency setpoint (reference value) in Hz after the ramp-function
generator.