Operating instructions

Issue 10/06 6 Commissioning
MICROMASTER 430
Operating Instructions (Compact)
65
6.4 Series commissioning
An existing parameter set can be transferred to a MICROMASTER 430 frequency
inverter using STARTER or DriveMonitor (refer to Section 4.1 "Establishing
communications MICROMASTER 430
STARTER").
Typical applications for series commissioning include:
1. If several drives are to be commissioned that have the same configuration and
same functions. A quick / application commissioning (first commissioning) must
be carried-out for the first drive. Its parameter values are then transferred to the
other drives.
2. When replacing MICROMASTER 430 frequency inverters.
6.5 Parameter reset of factory setting
User access level
1 Standard
Parameter filter
0 All parameters
Commissioning parameter
30 Factory setting
Factory reset
0 disabled
1 Parameter reset
The drive inverter carries-out a parameter reset (duration, approx. 10 s) and then
automatically exits the reset menu and sets:
P0970 = 0 : disabled
P0010 = 0 : ready
START
END
P0010 = 30
P0970 = 1
0
0
P0003 = 1
P0004 = 0
1
0