Technical Specifications

Table 13. Supported video resolution options (continued)
Resolution Refresh rate (Hz) Color depth (bits)
1920 x 1080 60 8, 16, 32
1920 x 1200 60, 75, 85 8, 16, 32
Environmental specifications
NOTE: For additional information about environmental certifications, see the Product Environmental Datasheet located
with the Documentation on www.dell.com/support/home.
Table 14. Continuous Operation Specifications for ASHRAE A2
Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
2953 ft)
1035°C (5095°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C minimum dew point to 80% RH with 21°C (69.8°F)
maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/300 m (33.8°F/984 Ft) above
900 m (2953 Ft)
Table 15. Continuous Operation Specifications for ASHRAE A3
Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
2953 ft)
540°C (41104°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C minimum dew point to 85% RH with 24°C (75.2°F)
maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/175 m (33.8°F/574 Ft) above
900 m (2953 Ft)
Table 16. Continuous Operation Specifications for ASHRAE A4
Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
2953 ft)
545°C (41113°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C minimum dew point to 90% RH with 24°C (75.2°F)
maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/125 m (33.8°F/410 Ft) above
900 m (2953 Ft)
Table 17. Common Environmental Specifications for ASHRAE A2, A3, A4
Allowable continuous operations
Maximum temperature gradient (applies to both
operation and non-operation)
20°C in an hour* (36°F in an hour) and 5°C in 15 minutes (41°F in 15
minutes), 5°C in an hour* (41°F in an hour) for tape
NOTE: * - Per ASHRAE thermal guidelines for tape hardware, these are
not instantaneous rates of temperature change.
Non-operational temperature limits -40 to 65°C (-104 to 149°F)
Non-operational humidity limits 5% to 95% RH with 27°C (80.6°F) maximum dew point
Maximum non-operational altitude 12,000 meters (39,370 feet)
Maximum operational altitude 3,048 meters (10,000 feet)
10 Technical specifications