Release Notes

2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Product Overview and Specifications
The Dell Basic Rack PDU distributes power to the devices in the rack.
OUTLETS The Rack PDU has five (5) 5-15 R outlets.
P
OWER CORD The Rack PDU has an IEC-320 C14 inlet and can be used with a detached power cord (not provided).
G761N
Electrical
Input connection IEC-320 C14 inlet
Acceptable input voltage 100–120 VAC
± 10%
Maximum input current (phase) 15 A (12 A UL(C-UL) derated)
Input frequency 50/60 Hz
Output voltage 100–120 VAC
± 10%
Output connections (5) 5-15 R
Maximum output current (outlet) 5-15 R; 12 A (UL(C-UL) derated)
5-15 R; 15 A (PSE)
Maximum output current (phase) 15 A (12 A UL(C-UL) derated)
Physical
Dimensions
(H x W x D)
23.97 x 4.36 x 9.29 cm
(9.44 x 1.72 x 3.66 in)
Shipping dimensions
(H x W x D)
28.60 x 21.03 x 13.00 cm
(11.26 x 8.28 x 5.12 in)
Weight 0.90 kg (2.00 lb)
Shipping weight 1.37 kg (3.01 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing
Compliance
Safety approvals UL(C-UL), PSE
ROHS Dell 6T198
EU DIRECTIVE 2002/95/EC–latest revision